Honeywell NOTIFIER FireWarden-100-2 Instruction Manual page 115

Fire alarm control panel
Table of Contents

Advertisement

Master Programming Level
view all the NAC zones without input assignments for NAC 1, NAC2, NAC 3 and NAC 4.
NOTE: If the NACs have been configured for Class A in the Setup option, only NAC1 and NAC 2
will display test information. NAC 3 and NAC 4 will display asterisks (*) and will not be included in
the test.
Pressing 2 while viewing the Program Check screen will display a screen similar to the following:
The Zone No Input screen allows the programmer to view the zones which have not been
programmed to at least one input device (not including general alarm Zone 00). The example in the
preceding screen indicates that Zones 05, 07, 09, 10 and 11 have been programmed to an
addressable module (control module in this example) with an address of 001 on loop 1 but have not
been programmed to any input devices. Use the up and down arrow keys to view all the zones
without input assignments.
Pressing 3 while viewing Program Check screen will cause a screen similar to the following to be
displayed:
The Zone No Output feature allows the programmer to view the zones which have not been
programmed to at least one output device (not including general alarm Zone 00). The example in
the preceding screen indicates that Zones 05, 07, 09, 10 and 11 have been programmed to an
addressable detector with an address of 001 on loop 1 but have not been programmed to any output
devices. Use the up and down arrow keys to view all the zones without output assignments.
FireWarden 100-2/E — P/N 52778:A 11/04/2005
ZONES NO INPUT
05 07 09 10 11 1M001
ZONES NO OUTPUT
05 07 09 10 11 1D001
Programming
115