Master Programming Level
Test Time Interval
CENTRAL STATION
Pressing 1 while viewing Primary/Secondary Screen #1 will cause the following screens to be
1=TEST TIME INT
2=ACCOUNT CODE
displayed:
3=24HR TST TIME
Primary/Secondary Screen #1
The test report sent to the Central Station phone number may be sent once every 6, 8, 12 or 24
hours. Select the desired Test Time Interval by pressing the corresponding digit in the screens
shown above.
Account Code
Pressing 2 while viewing Primary/Secondary Screen #1 will cause the following screen to be
displayed:
The Account Code, which is assigned by a Central Station, depends on the communication format
being used. The Account Code screen will have a flashing cursor in the lower left corner. Enter the
supplied account code using 0 - 9 and A- F keys.
FireWarden 100-2/E — P/N 52778:A 11/04/2005
TEST TIME INTERVAL
1=24 HOURS
2=12 HOURS
3=8 HOURS
Test Time Interval Screen #1
TEST TIME INTERVAL
1=6 HOURS
Test Time Interval Screen #2
ACCOUNT CODE
4 CHAR RANGE 0-F
Account Codes Screen
Programming
101