4: Loop Setup - Honeywell NOTIFIER FireWarden-100-2 Instruction Manual

Fire alarm control panel
Table of Contents

Advertisement

Programming
Zones Available
Pressing 2 while viewing Zone Setup Screen #3 will display a screen similar to the following:
ZONE SETUP
1=ZONE TYPES
2=ZONES AVAILABLE
3=ZONE MESSAGE
Zone Setup Screen #3
The display will show all of the zones that are still available for programming. Note that an up
and/or down arrow may appear in the upper right corner of the display, indicating that additional
screens of zone information exists. Press the up or down arrow key to view additional screens.
3.6.4 Loop Setup
Loop Setup allows the programmer to configure the SLC Loop for NFPA Style 4, 6 or 7 wiring and
PROGRAMMING
to select the loop protocol. Pressing 1 while viewing Programming Screen #2 will cause the
1=LOOP SETUP
following screen to be displayed:
2=SYSTEM SETUP
3=VERIFY LOOP
Programming Screen #2
Style
To program the SLC Style for the selected loop, press 1 for Style, while viewing Loop Setup
Screen. In the preceding example, the control panel is programmed for Style 4 SLC wiring as
indicated by the 4 to the right of Style in the display. To change the wiring style, press 1 to toggle
the display to read Style 6. Each press of the 1 key will cause the display to toggle between Style 4
and Style 6. Note that, when programming the Loop Style, the programmer can only select between
Style 4 and Style 6. To program a system for Style 7 wiring, the programmer must select the Loop
Setup for Style 6. Style 7 wiring is the same as Style 6 with the added requirement that each
addressable device on the loop must have a pair of isolator modules, one on each side.
NOTE: SLC Troubles:
Style 6, the trouble condition will latch at the FACP. When the SLC Loop has been repaired, the
Reset button must be pressed at the FACP (at least 2 minutes after the trouble has been repaired)
to clear the SLC trouble.
Loop Protocol
Loop Protocol refers to the SLC loop mode of operation. There are two Loop Protocols available,
each of which will work with the addressable devices in the FireWarden SLC manual.
Pressing 2 while viewing the Loop Setup Screen will toggle between CLIP and LiteSpeed Protocols.
Device Addressing
It is important to note that the NFW2-100 addressable device capacity is 99 detectors and 99
control/monitor modules. Newer devices can be set to addresses higher than 99 but these addresses
will not function with the NFW2-100.
76
ZONES AVAILABLE
01 02 03 04 05 06 07
08 09 10 11 12 13 14
15 16 17 18 19 20 21
1=STYLE
2=PROTOCOL
If the FACP reports an open fault on an SLC Loop programmed for
• LiteSpeed - This is the factory default setting. It results in quicker response times and is the
recommended protocol for use with this panel.
• CLIP (Classic Loop Interface Protocol) - Not recommended due to slower response times.
LOOP SETUP
LITESPEED
Loop Setup Screen
FireWarden 100-2/E — P/N 52778:A 11/04/2005
Master Programming Level
4

Advertisement

Table of Contents
loading

This manual is also suitable for:

Notifier firewarden-100-2e

Table of Contents