Programming
OPTION MODULES
1=ANNUNCIATORS/UDACT
2=ON BOARD DACT
3=PRINTER/PC
NO
Option Module Screen
112
Printer/PC
A Printer or a PC can be connected to the control panel. Pressing 3 while viewing the Option
Module Screen will cause the following screen to appear:
1=PRINTER NO SU
2=PRINTER SU
3=PC
Pressing 1 while viewing the Printer-PC Screen will program the control panel for an unsupervised
(NO SU) printer. The display will change to the Printer Baud Rate Screen as shown below.
Pressing 2 while viewing the Printer-PC Screen will program the control panel for a supervised
(SU) printer. Printer supervision, when enabled, will typically detect the removal of the printer
cable and will detect when the printer power has been turned off. Depending upon the brand of
printer, other errors such as paper empty or printer off-line may be detected.
The following screen will appear, which allows the programmer to select the baud rate for the
printer communication:
1=2400 BAUD
2=4800 BAUD
3=9600 BAUD
Pressing the number key corresponding to the desired baud rate (2 for 4800 Baud for example) will
program the control panel for the selected baud rate and return the display to the Option Module
Screen which will indicate Printer/PC PR4800 for a supervised printer installed at 4800 baud rate.
Pressing 3 while viewing the Printer-PC Screen will program the control panel for a PC connection.
The display will return to the Option Module Screen which will indicate Printer/PC PC for
personal computer installed.
NOTE: The FDU-80 and the Printer/PC use the same TB8 terminal block. Only one device can
be used at any one time. Setting any option in the Printer/PC screen to Yes will disable
communications with the FDU-80. The printer must be installed in the same room and within 50
feet of the FACP.
PRINTER-PC
Printer-PC Screen
PRINTER BAUD RATE
Printer Baud Rate Screen
FireWarden 100-2/E — P/N 52778:A 11/04/2005
Master Programming Level
NO
YES
NO