Checking Clearances; Preparing The Mounting Cutout - Siemens SIMATIC HMI Industrial Thin Client ITC1200 Operating Instructions Manual

Hmi device
Table of Contents

Advertisement

Installing and connecting the device
3.2 Preparing for installation
NOTICE
Damage due to overheating
Convection through the device is reduced when it is installed at an angle. This means that
the maximum permitted ambient temperature for operation is also reduced.
With sufficient forced ventilation, you can operate the device when installed at an angle up
to the maximum permitted ambient temperature for vertical installation.
Otherwise, the approvals and warranty will be voided.
3.2.4

Checking clearances

The following clearances around the device are required:
● Above and below the mounting cutout for ventilation purposes: 50 mm each
● Right and left of the mounting cutout for attaching the mounting clamps:
● At the rear in addition to the mounting cutout of the device: at least 10 mm
Note
Ensure compliance with the permissible ambient temperature when the device is installed
in a cabinet and especially in a closed enclosure.
3.2.5

Preparing the mounting cutout

Note
Stability of the mounting cutout
The material in the area of the mounting cutout must provide sufficient strength to guarantee
the enduring and safe mounting of the HMI device.
The force of the clamps or operation of the device may not lead to deformation of the
material in order to achieve the degrees of protection described below.
22
– When using metal mounting clamps: 15 mm each
– When using a clamping frame, independent of the type of mounting clamp used:
25 mm each
Industrial Thin Client ITC1200, ITC1500, ITC1900, ITC2200
Operating Instructions, 04/2013, A5E03474888-02

Advertisement

Table of Contents
loading

Table of Contents