Troubleshooting the DC Power Shelf Installation

Step 1
Step 2
Step 3
OL-11495-01
Use the following procedure to troubleshoot the DC power shelf if it is not
operating properly after installation.
Make sure that the power shelf is seated properly:
The jackscrew is tightened securely.
The captive screws on the flanges are tightened securely.
Make sure each power supply is seated properly:
Eject and reseat the PEM.
The captive screw on the ejector lever is tightened securely.
The power switch is in the on (1) position (2400 W only).
Make sure the router is powered on and that all power cords are connected
properly:
All power cables are securely connected to their terminal studs on the back
panel.
Each pair of PEM power cables is connected to a dedicated 60 A DC service.
The source DC circuit breaker is switched on.
The PEM circuit breaker is switched on (2000 W only).
If the circuit breaker does not stay switched on, check the polarity of the
power cables to the PEM.
A PEM trips its circuit breaker if it detects a reverse-polarity
Note
condition. This condition does not damage the PEM and it should
operate properly after the polarity is corrected.