Key Settings
Procedure
scale
Measurement
width
norml
Normal
Self-bottom hold
The selected digit flashes.
1 Set the operating mode selector to RUN.
2 Press the TEACH Key for 3 s.
The Sensor will enter function selection mode.
3 Set the Up Key to go to the hold.
oUt
Discrimination
outputs
4 Press the SET Key
The hold can now be selected.
5 Press the Up Key and select the hold.
p h
Peak hold
sb h
Self-peak hold
If the self-peak hold or self-bottom hold was selected, go to
step 6 and set the trigger level, otherwise go to step 8.
6 Press the SET Key.
The selected hold will be set.
7 Press the Right Key to move the cursor the digit to be
changed and press the Up Key to set the trigger level.
Default setting: The trigger level is set to 01.000 when the
measurement unit is V and 00.000 when the measurement
unit is mm.
00.000
Select the digit.
8 Press the SET Key.
The trigger level will be entered and the Sensor will return to
function selection mode.
9 Press the TEACH Key to return to RUN mode.
hys
Hysteresis
setting
b h
Bottom hold
Sample hold
sp h
Peak-to-peak hold
00.000
Set the value.
Section
4-2
hold
Hold
s h
pp h
03.000
43