Inspection for Loose Bottle Caps
HIGH Threshold Setting
Note "F.S." stands for full scale. In the case of the Z4LB-S10V2, for ex-
ample, the F.S. value is 10 mm.
Teaching value of reference workpiece
Fine Adjustment of Values
05.000
HIGH indicator
Display
LOW indicator
1 Set the operating mode selector to H.
The HIGH indicator will start flashing and the present HIGH
threshold will be displayed.
2 Set the workpiece and press the TEACH Key.
Teaching will be performed. The teaching value plus an
approximate value of 0.7% F.S. (see note) will be displayed
as the HIGH threshold.
HIGH threshold
The thresholds that are taught are reference values that can
be changed to desired values. Go to step 3 to change the
thresholds, otherwise go to step 5.
3 Press the Right Key to move the cursor to the digit to be
changed.
05.000
The selected
digit flashes.
4 Press the Up Key and change the value.
06.000
Section
05.000
07.000
1-1