Mitsubishi MELSEC-Q Series User Manual page 80

Programmable controller multiple cpu system
Hide thumbs Also See for MELSEC-Q Series:
Table of Contents

Advertisement

2
SYSTEM CONFIGURATION
2
- 27
2.1 System configuration
2.1.3 System configuration using Universal model QCPU as CPU No.1
* 8: When the Q8BAT is used for the Universal model QCPU, use the connection cable whose
connector part displays "A".
For details of connector part of a connection cable, refer to the following manual.
QCPU User's Manual (Hardware Design, Maintenance and Inspection)
* 9: For further information on PC CPU module, consult CONTEC Co., Ltd Tel: +81-6-6472-7130)
POINT
(1) When the multiple CPU system is configured using Q02UCPU as the CPU
No.1, only the following CPU modules can be used as the CPUs No.2.
• PC CPU module(PPC-CPU852(MS)-512)
• C Controller module
Note that the PC CPU module and C Controller module cannot be mounted
together.
(2) When the multiple CPU system is configured using the Universal model
QCPU (except Q02UCPU) as the CPU No.1, only the following CPU modules
can be used as the CPUs No.2 to No.4.
• Universal model QCPU(except Q02UCPU)
• High Performance model QCPU
• Process CPU
• Motion CPU(Q172DCPU,Q173DCPU)
• PC CPU module(PPC-CPU852(MS)-512)
• C Controller module
Note that the PC CPU module and C Controller module cannot be mounted
together.

Advertisement

Table of Contents
loading

Table of Contents