01.2004
12.9

Analog inputs/outputs

PNU
Parameter Name in OP1
*:conf-P
Description
P655
CUA AnaOut ActVal
*
Actual value output via the analog output of the CUSA
28FHex
Setting instruction: Enter the number of the parameter whose
Type=O2;
PKW: 1HEX=1
P656
CUSA AnalogOutGain
Gain factor of the analog output on the CUSA, see Section
290Hex
"Analog outputs"
Parameter values:
P656 = calculated output voltage when parameter value is set to
100 %
The calculation formula for the output voltage is as follows:
PWE
V
=
out
100
Note:
The output voltage at the analog output can be
maximum ± 10 V.
Type=I2;
PKW: 1HEX=0.01 V
P657
CUSA AnalogOutOffs
Offset of the analog output on the CU, cf. P656
291Hex
Type=I2;
PKW: 1HEX=0.01 V
P660
SCI AnalogInConf
Configuration of the analog inputs on the SCI1 boards, defining
294Hex
the type of input signals:
Parameter values Terminals
0: − 10 V ... + 10 V
1: 0 V ... + 10 V
2: 4 mA ... + 20 mA
Notes:
Only one signal can be processed per input. A choice of
voltage or current signals can be evaluated.
Voltage and current signals must be connected to different
terminals.
Settings 1 and 2 allow only unipolar signals to be used, i.e.
the internal process quantities are also unipolar.
When setting 2 is selected, an input current of < 2 mA
causes a shutdown on faults (open-wire monitoring).
Offset adjustment of the analog inputs is parameterized via
parameter P662.
Indices:
i001:
i002:
i003:
i004:
i005:
i006:
Precondition:
Type=O2;
PKW: 1HEX=1.0
Siemens AG
6SE7087-6CX86-2BA1
SIMOVERT MASTERDRIVES AFE
value is to be displayed.
PZD Gr.: 0
P656
P657
+
%
PZD Gr.: 0
PZD Gr.: 0
Terminals
X428/3, 6, 9
X428/5, 8, 11
−20 mA ... + 20 mA
0 mA ... + 20 mA
Sl11
Slave 1, analog input 1
Sl12
Slave 1, analog input 2
Sl13
Slave 1, analog input 3
Sl21
Slave 2, analog input 1
Sl22
Slave 2, analog input 2
Sl23
Slave 2, analog input 3
The associated SCB board must be logged on
via P090 or P091.
PZD Gr.: -
Operating Instructions
Range
# of Indices
[Unit]
Factory
Value Texts
Settings
0 to 999
303
−320.00 to
320.00
10.00
[V]
−100.00 to
100.00
0.00
[V]
0 to 2
6
i001=0
i002=0
i003=0
i004=0
i005=0
−10 V...+10 V
i006=0
0 V...+10 V
4 mA...20 mA
Parameter List
read:
_/_
write:
_/_
2 / BR
2 / BR
2 / BR
2 / BR
2 / BR
2 / BR
3 / BR
3 / BR
12-25