Guidelines For Rackmount Installation; Installation; Attaching The Strain-Relief Bracket - Enterasys Matrix E1 1H582-25 Installation Manual

E1 series
Table of Contents

Advertisement

3.7.1.1

Guidelines for Rackmount Installation

The installation site must be within reach of the network cabling and meet the requirements listed
below:
Appropriate grounded power receptacles must be located within seven feet of the location.
A temperature of between 5 C (41 F) and 40 C (104 F) must be maintained at the installation
site with fluctuations of less than 10 C (18 F) per hour.
CAUTION: To ensure proper ventilation and prevent overheating, leave a minimum
clearance space of 5.1 cm (2.0 in) at the left, right, and rear of the device.
WARNING: Before installing the device into a rack, ensure that the rack can support the
device(s) without compromising the stability of the rack. Otherwise, personal injury
and/or equipment damage may result.
3.7.1.2

Installation

Rack mounting the device involves the following:

Attaching the strain-relief bracket

Rack mounting the device (attaching the mounting brackets and fastening the device to the rack)
3.7.2
Attaching the Strain-Relief Bracket
To attach the strain-relief bracket to the device, refer to
1. Locate the strain-relief bracket
management kit.
CAUTION: Do not attempt to attach the strain-relief bracket with screws other than the
M4 x 6 mm screws included with the device. Use of longer screws may damage the unit.
Figure 3-8
and four M4 x 6 mm pan-head screws
Installing the Device
and proceed as follows:
in the cable
Hardware Installation