13. OPTIONS AND AUXILIARY EQUIPMENT
13.2 Auxiliary equipment
Always use the devices indicated in this section or equivalent. To comply with the EN Standard or UL/C-UL
(CSA) Standard, use the products which conform to the corresponding standard.
13.2.1 Selection example of wires
(1) Wires for power supply wiring
The following diagram shows the wires used for wiring. Use the wires given in this section or equivalent.
www.DataSheet4U.com
The following table lists wire sizes. The wires used assume that they are 600V vinyl wires and the wiring
distance is 30m max. If the wiring distance is over 30m, choose the wire size in consideration of voltage
drop.
Refer to section 3.11 for connection with the connector (CNP1, CNP2).
The servo motor side connection method depends on the type and capacity of the servo motor. Refer to
section 3.8.
To enable the built-in regenerative brake, connect the wiring across D-P. (Refer to section 3.7.2 for the
connection method.)
To comply with the UL/C-UL (CSA) Standard, use UL-recognized copper wires rated at 60
more for wiring.
Servo amplifier
MR-E-10A-QW003
MR-E-20A-QW003
MR-E-40A-QW003
MR-E-70A-QW003
MR-E-100A-QW003
MR-E-200A-QW003
Note. Use the heat-resistant PVC cable (rated 105
more .
1) Power supply lead
Power supply
Regenerative option
3) Regenerative option lead
Note. When using the regenerative option, always remove the wiring across D-P.
Table 13.1 Selection example of wires
1) L
L
L
3) U V W
1
2
3
1.25 (AWG16)
2 (AWG14)
2 (AWG14)
(Note) 2.5 (AWG14)
(Note) 2.5 (AWG14)
2) Motor power supply lead
Servo amplifier
L
U
1
L
V
2
L
W
3
(Note)
D
C
P
Encoder cable (refer to section 13.1.2)
2
(Note) Wires [mm
]
4) P C D
2 (AWG14)
(221 ) or more ), if AWG14 cable is used in ambient temperature 40
13 - 29
Servo motor
U
V
W
Motor
4) Electromagnetic
brake lead
Electro-
B1
magnetic
brake
B2
Encoder
5) B1 B2
1.25 (AWG16)
(140 ) or
(104 ) or