Features In The D9412Gv3 And D7412Gv3; Sdi Molex Connector; Tip And Ring Posts; Telephone Line Sniff - Bosch D9412GV3 Operation And Installation Manual

Hide thumbs Also See for D9412GV3:
Table of Contents

Advertisement

.
3.3
Features in the D9412GV3 and
D7412GV3
3.3.1

SDI Molex Connector

Use the SDI Molex Connector to easily connect an
SDI device to the SDI bus without needing to
disconnect wires connected to the SDI terminals.
Possible applications include:
Connecting a DX4010i to program the control
panel with Remote Programming Software (RPS)
at the premises
Connecting a keypad to test the control panel.
Do not connect the D5200 Programmer to
the SDI Molex connector.
Control panel firmware v8.11 or later
does not support the D5200.
UL requires that the DX4010i be used for
programming only.
3.3.2

Tip and Ring Posts

The tip and ring posts allow connecting a phone or
buttset for the purpose of troubleshooting
communications between the control panel and the
central station. This connection allows monitoring of
the dial tone, handshaking tones from the receiver,
and communications signals.
3.3.3

Telephone Line Sniff

The D9412GV3 and D7412GV3 control panels
monitor the phone line for the programmed
supervision interval before indicating a phone line
trouble.).
3.3.4

Points

The Bosch Security Systems, Inc. D9412GV3 Control
Panel provides up to 246 points of protection. The
D7412GV3 Control Panel provides up to 75 points of
protection. Point programming parameters determine
the control panel's response to open and shorted
conditions on the sensor loop for the point. Several
options allow individual point programming to custom-
fit the protection to the installation.
Points 1 to 8 are located on the circuit board (on-
board points). They are standard sensor loops. The
remaining off-board points are POPIT points using
D8128D OctoPOPITs, D8125 POPEX Modules and
D9127 POPITs, or the ISW-D8125CW-V2
Commercial Wireless Interface Module.. MUX devices
can also be used with the D8125MUX.
Bosch Security Systems, Inc. | 10/10 | F01U143070-03
D9412GV3/D7412GV3 | Operation and Installation Guide | 3.0
3.3.5
The D9412GV3 supports up to 32 areas. The
D7412GV3 supports up to 8 areas. You can assign all
points to a single area or distribute them over all
supported areas.
The control panel is armed and disarmed by area,
and several areas can be armed and disarmed with
one menu function. A passcode can also be assigned
an authority level that allows a user to arm an area
from a remote keypad in another area.Assigning each
area its own account number creates up to 32
separate accounts in the D9412GV3, and up to 8
separate accounts in the D7412GV3. Assigning the
same account number to different areas groups them
together in a single account.
Area options include exit tone and delay, separate fire
and burglary outputs, and multiple opening and
closing windows. Area type can be used to create
area interdependencies for arming purposes.
3.3.6
The control panel uses a built-in digital communicator
to send reports to the receiver. The control panel
sends reports in either the Modem IIIa
Contact ID format. All software versions for the D6600
can be used with the control panel.
The control panel connects to an RJ31X or RJ38X
jack for telephone line seizure. Connecting to the
RJ31X complies with FCC regulations for using the
public telephone network. The control panel can be
programmed to direct reports to four separate
telephone numbers. Adding the D928 Dual Phone
Line Switcher Module allows connecting and
supervising a second telephone line.
The system can route groups of Event Reports to four
different destinations. Each report group can be
programmed to send reports to one or more
destinations. Primary and backup reporting paths can
be programmed for each destination and each report
group. A custom option allows specification of
individual Event Reports to be sent.
Any points programmed as fire
supervisory points are latching.

Areas and Accounts