D7024 | Operation and Installation Guide | 6.0 Programming

6.0 Programming

After any programming change, and especially after remote programming changes, a complete functional
checkout of the control panel's operation is required. Hazards to life and property can occur if the system
is not tested to detect possible improper programming.
When programming the system, enter only valid information within the ranges specified in the program-
ming table. Incorrect programming causes improper system operation. While using built-in programming,
invalid input values might not be rejected in every case. Ensure that only the intended values are entered
while programming to prevent improper system operation.
6. 1

Point Programming

6. 1 . 1

Point Functions Overview

Each point in the system can be programmed with its own characteristics. Point functions simplify the point
programming by allowing you to define a common set of characteristics for similar points, and assigning those
characteristics to selected points as a point function. There are 16 point functions, each with programmable
configuration features (such as fire, waterflow, and so on), local only operation, silencing, and loop response.
Each point is assigned to use the characteristics of one point function and then programmed for additional
characteristics, such as response to an open circuit, enabled status, output zone, verification, latching, and point
description.
Before programming the control panel, determine the types of functions required and map the input points
to the functions.
For example, you can determine you have the following functions:
1 = Pull Station
2 = Smoke Detector
3 = Reset Keyswitch
4 = Silence Keyswitch
5 = Supervisory Input
6 = Monitor Input
7 = Local Test
8 = Waterflow Sensor
Refer to Table 16 for the characteristics that correlate with each function.
Table 16:

Point Function Characteristics

Function
1. Pull Station
2. Smoke Detector
3. Reset Keyswitch
4. Silence Keyswitch
5. Supervisory Input
6. Monitor Input
7. Local Test
8. Waterflow Sensor
30
Configuration
Local Only?
Fire
No
Fire
No
Reset
Yes
Silence
Yes
Supervisory
No
Monitor
Yes
Fire
Yes
Waterflow
No
Silenceable?
Loop Resp.
No
Fast
No
Fast
No
Fast
No
Fast
Yes
Fast
Yes
Fast
Yes
Fast
No
Programmed
Bosch | 7/05 | 31499J