Dc Power Grounding Requirements And Warning - Juniper JSA7500 Secure Analytics Hardware Manual

Hide thumbs Also See for JSA7500:
Table of Contents

Advertisement

AC Power Electrical Safety Guidelines | 51
DC Power Electrical Safety Guidelines | 53

DC Power Grounding Requirements and Warning | 56

DC Power Wiring Sequence Warning | 57

DC Power Grounding Requirements and Warning

An insulated grounding conductor that is identical in size to the grounded and ungrounded branch
circuit supply conductors but is identifiable by green and yellow stripes is installed as part of the branch
circuit that supplies the device. The grounding conductor is a separately derived system at the supply
transformer or motor generator set.
WARNING: When you install the device, the ground connection must always be made
first and disconnected last.
Waarschuwing Bij de installatie van het toestel moet de aardverbinding altijd het eerste
worden gemaakt en het laatste worden losgemaakt.
Varoitus Laitetta asennettaessa on maahan yhdistäminen aina tehtävä ensiksi ja
maadoituksen irti kytkeminen viimeiseksi.
Attention Lors de l'installation de l'appareil, la mise à la terre doit toujours être
connectée en premier et déconnectée en dernier.
Warnung Der Erdanschluß muß bei der Installation der Einheit immer zuerst hergestellt
und zuletzt abgetrennt werden.
Avvertenza In fase di installazione dell'unità, eseguire sempre per primo il collegamento
a massa e disconnetterlo per ultimo.
Advarsel Når enheten installeres, må jordledningen alltid tilkobles først og frakobles sist.
Aviso Ao instalar a unidade, a ligação à terra deverá ser sempre a primeira a ser ligada, e
a última a ser desligada.
¡Atención! Al instalar el equipo, conectar la tierra la primera y desconectarla la última.
Varning! Vid installation av enheten måste jordledningen alltid anslutas först och
kopplas bort sist.
56

Advertisement

Table of Contents
loading

This manual is also suitable for:

Jsa3800Jsa5800Jsa7800

Table of Contents