Dc Power Electrical Safety Guidelines - Juniper JSA7500 Secure Analytics Hardware Manual

Hide thumbs Also See for JSA7500:
Table of Contents

Advertisement

RELATED DOCUMENTATION
General Electrical Safety Guidelines and Warnings | 47
Prevention of Electrostatic Discharge Damage | 49
AC Power Electrical Safety Guidelines | 51

DC Power Electrical Safety Guidelines | 53

DC Power Electrical Safety Guidelines

• A DC-powered device is equipped with a DC terminal block that is rated for the power requirements
of a maximally configured device.
NOTE: To supply sufficient power, terminate the DC input wiring on a facility DC source that
is capable of supplying:
• Minimum of 60 A at –38 VDC
Incorporate an easily accessible disconnect device into the facility wiring. Be sure to connect the
ground wire or conduit to a solid office earth ground. A closed loop ring is recommended for
terminating the ground conductor at the ground stud.
• Run two wires from the circuit breaker box to a source of 38 VDC.
• A DC-powered device that is equipped with a DC terminal block is intended only for installation in a
restricted access location. In the United States, a restricted access area is one in accordance with
Articles 110-16, 110-17, and 110-18 of the National Electrical Code ANSI/NFPA 70.
NOTE: Primary overcurrent protection is provided by the building circuit breaker. This breaker
must protect against excess currents, short circuits, and earth grounding faults in accordance
with NEC ANSI/NFPA 70.
• Ensure that the polarity of the DC input wiring is correct. Under certain conditions, connections with
reversed polarity might trip the primary circuit breaker or damage the equipment.
• For personal safety, connect the green and yellow wire to safety (earth) ground at both the device
and the supply side of the DC wiring.
53

Advertisement

Table of Contents
loading

This manual is also suitable for:

Jsa3800Jsa5800Jsa7800

Table of Contents