6802800U74-AN
Chapter 4: Hardware Installation
Figure 53: MTS LVD Kit Backplate Plugs
5 Mount the LVD housing to the intended location, i.e. on top of the MTS as shown in Figure
below, using a hammer for snapping in the screw.
Figure 54: Mounting the MTS LVD Kit
NOTICE: The plug fits into any Ø7 mm hole. Center diameter between the two rivet plugs
is 90 mm.
6 Locate the Power connector on the Site Controller and disconnect this.
7 Plug the LVD controller cable into the now empty power slot and plug the existing power plug
just removed in step above into the empty socket on the controller cable.
8 Secure LVD controller cable using cable ties to the best possible routing toward the LVD relay.
Avoid any potential damages on cable due to sharp edges etc.
9 Switch power on.
10 Check if the relay is engaged, when MTS 4 is powered up.
11
4