Benefit
Description
Setting
Note
Benefit
Description
Setting
Effect
Siemens Building Technologies
HVAC Products
5.60 Actuator running time heating circuit
• Setting the actuator running time
Allows adjustments to be made to supplier-specific actuator running times.
Setting range
30...873
The actuator running time is the period of time the actuator requires to travel from one
end position to the other.
D.h.w. EXP
5.61 Maximum nominal setpoint of the d.h.w.
temperature (TBWmax)
• Setting can be limited by the enduser
• Reduced risk of scalding
• Minimized proneness to buildup of lime
Function for limiting the nominal setpoint of the d.h.w. temperature.
Setting range
8...80
The setting will ensure maximum limitation of the nominal d.h.w. temperature setpoint
(setting 26).
0
10
20
30
26
Setting "Nominal setpoint of the d.h.w. temperature"
770
Setting "Reduced setpoint of the d.h.w. temperature"
750
Setting "Maximum nominal setpoint of the d.h.w. temperature"
EXP
Basic Documentation RVP540 / RVP550
Description of the EXP settings
Unit
s
Unit
°C
40
50
60
70
80
Factory setting
120
Factory setting
60
90
100
120
130
140
317/348
CE1P2488en
18.10.2002
°C