4.204 Minimum limitation of the flow temperature
setpoint (TVmin)
• Prevents too low flow temperatures
Minimum and maximum limitation define the range within which the flow temperature
setpoint may vary.
Setting range
8...TVmax
TVmax
Maximum limitation of the flow temperature setpoint (setting on operating line 724)
TV
max
akt
min
0
10
20
TVw Current flow temperature setpoint
723
Minimum limitation of the flow temperature setpoint
724
Maximum limitation of the flow temperature setpoint
The setting will make certain that the flow temperature setpoint will not fall below a
minimum level.
If the flow temperature setpoint demanded by the heating circuit reaches the minimum
limit and the outside temperature rises, the flow temperature setpoint will be maintained
at that limit, in other words, it will not be allowed to fall below it. This may lead to exces-
sive room temperatures.
Basic Documentation RVP540 / RVP550
Description of the heating engineer settings
Unit
°C
TVw
30
40
50
60
Factory setting
8
70
80
90
100
223/348
CE1P2488en
18.10.2002
°C