4.75 Temperature differentials collector /
swimming pool
• Understanding the current operating state of the plant
• Understanding the control processes
The temperature differential between collector and swimming pool will automatically be
displayed on this operating line.
Display
--- / -50...350
Temperature differential collector 1 (B6) and swimming pool (B13).
Temperature differential collector 2 (B61) and swimming pool (B13).

Hours run counter

4.76 Hours run of collector pumps Q5 and Q16

• Overview of the number of collector pump operating hours
• Parameter for making energy calculations and plant analyses
The total number of collector pump operating hours since the last reset will automati-
cally be displayed on this operating line.
Display
0...999'999
Number of operating hours of collector pump 1 (Q5)
(collector 1 with sensor B6)
Number of operating hours of collector pump 2 (Q16)
(collector 2 with sensor B61)
To reset the hours run counter to 0, press the + / - buttons simultaneously for 3 sec-
onds.
Basic Documentation RVP540 / RVP550
Description of the heating engineer settings
Unit
K
Unit
h
145/348
CE1P2488en
18.10.2002