Commissioning; Functional Checks - Siemens SIGMAGYR RVP540 Basic Documentation

Heat energy manager
Hide thumbs Also See for SIGMAGYR RVP540:
Table of Contents

Advertisement

Sensor designations
Prerequisites
Siemens Building Technologies
HVAC Products
Sensor
Function (use)
B1
Heating circuit flow temperature sensor
B2
Temperature sensor of oil- / gas-fired boiler
B21
Heat pump flow temperature sensor
B22
Temperature sensor of wood-fired boiler
B3
D.h.w. temperature sensor 1
B31
D.h.w. temperature sensor 1
B32
D.h.w. temperature sensor 3
B33
D.h.w. temperature sensor 5
B4
Buffer storage tank temperature sensor 1
B41
Buffer storage tank temperature sensor 2
B42
Buffer storage tank temperature sensor 3
B43
Buffer storage tank temperature sensor 4
B6
Solar collector temperature sensor 1
B61
Solar collector temperature sensor 2
B62
Solar collector flow temperature sensor
B63
Solar flow temp. sensor for yield measurement
B64
Solar return temp. sensor for yield measurem.
B7
Return temperature sensor oil / gas
B71
Return temperature sensor heat pump
B72
Return temperature sensor wood
B73
Return temperature sensor heating circuit
B8
Flue gas temperature sensor
B9
Outside temperature sensor
B10
Common flow temperature sensor
B13
Sensor for solar swimming pool heating
M
Ground sensors, H1, U1, P1
H1
Contact or DC 0...10 V input
U1
DC 0...10 V output
P1
PWM output
A6
PPS data
MD
PPS ground
DB
LPB data
MB
LPB ground

2.3 Commissioning

To commission the controller:
1. Make certain that mounting and electrical installation are in compliance with the
relevant requirements.
2. Enter all plant-specific settings as described in section "Parameter settings".
3. Reset the attenuated outside temperature (see operating line 34).
4. Make the functional checks.

2.3.1 Functional checks

To facilitate commissioning and fault tracing, the controller allows output and input tests
to be made. With these tests, the controller's inputs and outputs can be checked.
The output test is described on operating line 210, the input test on operating line 211
(heating engineer level).
Additional help in connection with the functional check is provided by the functional
tests of the individual blocks (operating lines 296, 349, 395, 545 and 745) and the out-
put tests (operating lines 888 and 894).
Basic Documentation RVP540 / RVP550
Handling
Types of sensors
Strap-on sensor LG-Ni 1000
Strap-on sensor LG-Ni 1000
Strap-on sensor LG-Ni 1000
Strap-on sensor LG-Ni 1000
Strap-on sensor LG-Ni 1000
Strap-on sensor LG-Ni 1000
Strap-on sensor LG-Ni 1000
Strap-on sensor LG-Ni 1000
Strap-on sensor LG-Ni 1000
Strap-on sensor LG-Ni 1000
Strap-on sensor LG-Ni 1000
Strap-on sensor LG-Ni 1000
LG-Ni 1000/Pt 1000
LG-Ni 1000/Pt 1000
Strap-on sensor LG-Ni 1000
LG-Ni 1000/Pt 1000
LG-Ni 1000/Pt 1000
Strap-on sensor LG-Ni 1000
Strap-on sensor LG-Ni 1000
Strap-on sensor LG-Ni 1000
Strap-on sensor LG-Ni 1000
Pt 1000
LG-Ni 1000/NTC600
Strap-on sensor LG-Ni 1000
Strap-on sensor LG-Ni 1000
CE1P2488en
18.10.2002
27/348