Line
Function
Hours run counter
311
Number of operating hours collector pump 1 (output Q5)
To reset to 0, press the + / - buttons simultaneously for 3 seconds
312
Number of operating hours collector pump 2 (output Q16)
To reset to 0, press the + / - buttons simultaneously for 3 seconds
313
Number of operating hours pump K12
To reset to 0, press the + / - buttons simultaneously for 3 seconds
314
Number of operating hours diverting valve K8
To reset to 0, press the + / - buttons simultaneously for 3 seconds
315
Number of operating hours swimming pool heating K18
To reset to 0, press the + / - buttons simultaneously for 3 seconds
Swimming pool heating
317
Setpoint temperature swimming pool
318
Actual value of swimming pool temperature B13
---
No value available
319
Temperature differential swimming pool ON
320
Temperature differential swimming pool OFF
321
Maximum swimming pool charging temperature
322
Heat exchanger-pump operation for swimming pool
1
Alternatively
2
Parallel
323
Measured value correction swimming pool sensor B13
Functions
324
Selection of type of collector sensor B6 / B61
1
LG-Ni 1000
2
Pt 1000
325
Measured value correction collector sensor B6
326
Measured value correction collector sensor B61
327
Measured value correction collector flow sensor B62
328
Heat exchanger pump operation for partial diagram Sol 5
1
Alternative operation
2
Parallel operation
329
Temperature differential ON heat exchanger 1
330
Temperature differential OFF heat exchanger 1
331
Temperature differential ON heat exchanger 2
332
Temperature differential OFF heat exchanger 2
333
Priority with 2 heat exchangers
1
No priority
2
Rel. priority buffer storage tank (heat exchanger 1)
3
Abs. priority buffer storage tank (heat exchanger 1)
4
Rel. priority d.h.w. storage tank (heat exchanger 2)
5
Abs. priority d.h.w. storage tank (heat exchanger 2)
Solar yield / discharge measurement
338
Type of antifreeze agent
1
None (only water)
2
Ethylenglykol
3
Propylenglykol
4
Mixture of Ethylen and Propylenglykol
339
Concentration of antifreeze agent
340
Pulse value of flow measurement
Supported 1, 2.5, 10, 25, 100 liters / pulse
341
Volumetric flow solar pump
342
Selection of type of sensor for solar yield measurement
(B63 and B64)
1
LG-Ni 1000
2
Pt 1000
343
Actual value of solar flow temperature B63
---
No value available
344
Actual value of solar return temperature B64
---
No value available
Siemens Building Technologies
HVAC Products
Basic Documentation RVP540 / RVP550
Handling
Range
Unit
0...999'999
h
0...999'999
h
0...999'999
h
0...999'999
h
0...999'999
h
0...line 321
°C
–50...350
°C
Line 320...40
K
0...line 319
K
20...95
°C
1 / 2
-10.0...10.0
K
1...2
-10.0...10.0
K
-10.0...10.0
K
-10.0...10.0
K
1...2
Line 330...40
°C
0...line 329
°C
Line 332...40
°C
0...line 331
°C
1...5
1...4
1...100
%
1.0 / 2.5 / 10 /
25 / 100
10...1500
Liters / h
1 / 2
–50...350
°C
–50...350
°C
Resolution
Factory
setting
1
0
1
0
1
0
1
0
1
0
1
25
1
1
8
1
4
1
35
1
1
0.1
0.0
1
1
0.1
0.0
0.1
0.0
0.1
0
1
2
1
8
1
4
1
8
1
4
1
4
1
1
1
30
10.0
1
200
1
2
1
1