4.72 Actual value of collector flow temperature
B62
• Visualization of the current collector flow temperature
The collector flow temperatures is visualized to better understand the current operating
state of the plant.
Display
-50...350
The current collector flow temperature (sensor B62) in [°C] will automatically be dis-
played on this operating line.
The display is already readjusted by the measured value correction (operating line
327).
– – –
No value available
The sensor is to be located either in the solar collector circuit very close to the diverting
valve (as with Sol3) or on the flow of the secondary circuit (as with Sol4).
Sol 3
B6
Q5
1
0
K9
B62
4.73 Maximum values B6 and B61 of the collector
temperature
• Display of the highest temperature measured on the collector
• Knowledge of the relevant stationary temperature of the collector
The highest collector temperature measured since the last reset will automatically be
displayed on this operating line.
Display
-50...350
Maximum value of collector temperature 1 (sensor B6) in [°C]
Maximum value of collector temperature 2 (sensor B61) in [°C]
The maximum value of the collector temperature can be reset to the currently acquired
collector temperature by simultaneously pressing the + / - buttons for 3 seconds.
Basic Documentation RVP540 / RVP550
Description of the heating engineer settings
Unit
°C
Sol 4
B6
Q5
B62
K9
Unit
°C
CE1P2488en