Display Of Partial Diagram "Combi Storage Tank; Selection Of Partial Diagram "Heating Circuit - Siemens SIGMAGYR RVP540 Basic Documentation

Heat energy manager
Hide thumbs Also See for SIGMAGYR RVP540:
Table of Contents

Advertisement

Description
Setting
Effect
Selection
Note
Description
Setting
Effect
86/348
Siemens Building Technologies
HVAC Products
4.8
Display of partial diagram "Combi storage
tank"
The partial diagram of the combi storage tank can only be slightly changed within the
relevant basic diagram. If a completely different partial diagram of the combi storage
tank is required, another basic diagram with an adequate partial diagram must be se-
lected.
Setting range
0...6
The partial diagram number of the combi storage tank that is contained in the selected
basic diagram will automatically be displayed on this operating line. The numbers have
the following meaning:
0
No partial diagram available.
Parameter block "Combi storage tank" will be hidden.
1...6
Partial diagrams according to the partial diagram library (documents
CE1P2489en and CE1P2490en).
The partial diagrams with diverting valve Q3 can be replaced by a partial diagram with-
out a diverting valve (according to the table given below).
Diagram that can be modified
(with Q3):
KoSp 4
KoSp 5
KoSp 6
The diverting valve of combi storage tank partial diagrams 4 through 6 can be replaced
by a charging pump (also Q3, see operating line 193). In that case, the partial diagram
number does not change.
4.9

Selection of partial diagram "Heating circuit"

Partial diagram "Heating circuit" as defined by the basic diagram can be replaced by
another partial diagram that requires the same maximum number of terminals at the
most, or it can be hidden.
Setting range
0...3
The currently selected partial diagram number will automatically be displayed on this
operating line. The numbers have the following meaning:
0
No partial diagram selected.
Parameter block "Heating circuit" will be hidden.
1...3
Partial diagrams according to the partial diagram library (documents
CE1P2489en and CE1P2490en).
Basic Documentation RVP540 / RVP550
Description of the heating engineer settings
Unit
Can be replaced by partial diagram number
(without Q3):
KoSp 1
KoSp 2
KoSp 3
Unit
Factory setting
0
Factory setting
0
CE1P2488en