The time switch program can be set with the QAW70 room unit.
But this is possibly only if operating mode Auto

Free time switch program

• The free time switch program serves as a switching criterion for a number of func-
tions.
The time switch program consists of switching times that can be entered for the week-
days or the 7-day block.
It operates independently of the time switch programs for space heating and d.h.w.
The free time switch program can have an impact on the following functions:
• Forced charging of the buffer storage tank with the heat pump (operating line 475)
• D.h.w. circulating pump (operating line 772)
• Auxiliary functions 23, K13 (operating line 169)
• Additional pump kick for water / brine pump (operating line 427)

3.12 Preselection of weekday

With this setting, you select the weekdays or the 7-day block for which the switching
times of the time switch program apply.
Setting range
1-7
1...7
The principle is the same as that used with "Time switch program space heating" (refer
to the diagrams and the tip on page 64).

3.13 Switching times

With this setting, you define the switching times for the free time switch program.
Setting range
- -:- - / 00:00...24:00
First, select the weekday (operating line 12) for which the switching times shall be en-
tered!
Basic Documentation RVP540 / RVP550
Description of the enduser settings
Temperature setpoint
Setpoint of knob
Reduced setpoint
Setpoint of knob
Reduced setpoint
Setpoint of knob
Reduced setpoint
Unit
7-day block
Individual days
Unit
h : min
Standard
06:00
22:00
– – : – –
– – : – –
– – : – –
– – : – –
is selected on the controller.
Factory setting
See "Program overview"
below
CE1P2488en