Siemens SIGMAGYR RVP540 Basic Documentation page 36

Heat energy manager
Hide thumbs Also See for SIGMAGYR RVP540:
Table of Contents

Advertisement

Line
Function
161
Solar heat exchanger diverting valve inverted K¯8
(ZuFu15)
- - -
None
¯
101...110
Relay K
8 connected to relay terminal Q101...110
162
Solar diverting valve inverted K¯9 (ZuFu16)
- - -
None
¯
101...110
Relay K
9 connected to relay terminal Q101...110
169
Output K13 for free time switch program (ZuFu23)
- - -
None
101...110
Relay K13 connected to relay terminal Q101...110
170
Electric immersion heater buffer storage tank K16
(ZuFu24)
- - -
None
101...110
Relay K16 connected to relay terminal Q101...110
171
Electric immersion heater d.h.w. storage tank K6
(ZuFu25)
- - -
None
101...110
Relay K6 connected to relay terminal Q101...110
172
D.h.w. diverting valve inverted Q¯3 (ZuFu26)
- - -
None
101...110
Valve / pump Q
173
Heat generation lock Y4 (ZuFu27)
- - -
None
101...110
Relay Y4 connected to relay terminal Q101...110
174
Heat generation lock inverted Y¯4 (ZuFu27)
- - -
None
¯
101...110
Relay Y
4 connected to relay terminal Q101...110
175
Solar swimming pool heating K18 (ZuFu28)
- - -
None
101...110
Relay K18 connected to relay terminal Q101...110
176
Solar swimming pool heating inverted K¯18 (ZuFu28)
- - -
None
¯
101...110
Relay K
18 connected to relay terminal Q101...110
177
Solar swimming pool heating sensor B13 (ZuFu28)
- - -
None
101...109
Sensor B13 connected to sensor terminal B101...109
Miscellaneous
193
D.h.w. heating with charging pump or diverting valve Q3
0
charging pump
1
Diverting valve
194
Setpoint and time switch program for d.h.w. heating with
a BMU
0
No
1
Yes
195
Function of system pump Q14
1
For heating circuit only
2
For heating circuit and d.h.w.
3
With external demand
General
Diagnosis configuration
200
Display of relay terminal assignment
Query with the + / - buttons
201
Display of sensor terminal assignment
Query with the + / - buttons
202
Display of configuration errors
Blank = no error
203
Display of diagram identification number part 1
204
Display of diagram identification number part 2
205
Display of diagram identification number part 3
206
Display of diagram identification number part 4
36/348
Siemens Building Technologies
HVAC Products
¯
3 connected to relay terminal Q101...110
Basic Documentation RVP540 / RVP550
Handling
Range
Unit
101...110
101...110
101...110
101...110
101...110
101...110
101...110
101...110
101...110
101...110
101...109
0 / 1
0 / 1
1...3
101...110
101...109
1...99
0...99'999'999
0...99'999'999
0...99'999'999
0...99'999'999
Resolution
Factory
setting
1
- - -
1
- - -
1
- - -
1
- - -
1
- - -
1
- - -
1
- - -
1
- - -
1
- - -
1
- - -
1
- - -
1
- - -
1
0
1
1
1
1
1
1
1
1
1
CE1P2488en
18.10.2002

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sigmagyr rvp550

Table of Contents