Selection Of Partial Diagram "Wood-Fired Boiler; Selection Of Partial Diagram "Heat Pump - Siemens SIGMAGYR RVP540 Basic Documentation

Heat energy manager
Hide thumbs Also See for SIGMAGYR RVP540:
Table of Contents

Advertisement

Description
Setting
Effect
Description
Setting
Effect
84/348
Siemens Building Technologies
HVAC Products
4.4
Selection of partial diagram "Wood-fired
boiler"
The partial diagram "Wood-fired boiler" defined by the basic diagram can be replaced
by another partial diagram that requires the same number of terminals at the most, or it
can be hidden.
Setting range
0...5
The currently selected partial diagram number will automatically be displayed on this
operating line. The numbers have the following meaning:
0
No partial diagram selected.
Parameter block "Wood-fired boiler" will be hidden.
The basic diagram number remains the same.
The setting is useful when replacing the heat source or when a section of the
plant is already in operation and the wood-fired boiler is supplied later.
1...5
Partial diagrams according to the partial diagram library (documents
CE1P2489en and CE1P2490en).
4.5

Selection of partial diagram "Heat pump"

The partial diagram "Heat pump" defined by the basic diagram can be replaced by an-
other partial diagram that requires the same maximum number of terminals, or it can be
hidden.
Setting range
0...5
The currently selected partial diagram number will automatically be displayed on this
operating line. The numbers have the following meaning:
0
No partial diagram selected.
Parameter block "Heat pump" will be hidden.
The basic diagram number remains the same.
The setting is useful when replacing the heat source or when a section of the
plant is already in operation and the heat pump is supplied later.
1...5
Partial diagrams according to the partial diagram library (documents
CE1P2489en and CE1P2490en).
Basic Documentation RVP540 / RVP550
Description of the heating engineer settings
Unit
Factory setting
0
Unit
Factory setting
0
CE1P2488en