8.2 LED display
8.2.3

STATE / OVERLOAD LED

LED ST/OL
Lights up
Flashes
Flashes
Flashes
alternately
green / yellow
Lights up
Flashes red
164
Status of the
3RW50 soft starter
Operation
green
Ramp-up or ramp-down
time active
green
Stop
Off
Stop - not ready to start •
yellow
Operation with motor
overload warning
Stop with motor
overload warning
yellow
Stop with motor
overload error
Motor operating state
The ramp-up time comes to an end and the motor is
running.
Motor is ramping up or ramping down.
Motor is switched off but might still be rotating.
Motor is ready to start.
Motor is switched off but might still be rotating.
Motor is not ready to start. An ON command will cause
an error while at least one of the starting conditions is
not fulfilled, e.g.:
Supply voltage of motor missing.
Motor has started up and is running.
A motor overload warning exists, e.g.:
Motor is too hot
Motor has decelerated to zero speed and shut down.
A motor overload warning exists, e.g.:
Motor is too hot
Motor has decelerated to zero speed and shut down due to
an overload error.
A motor overload error exists, e.g.:
Motor is too hot
Temperature sensor wire break
Temperature sensor short circuit
Manual, 09/2019, A5E35628455002A/RS-AA/001