Siemens SIRIUS 3RW50 Manual page 171

Industrial controls, soft starters and semiconductor switching devices
Table of Contents

Advertisement

Error
Error
No.
1)
1479
Phase control failure
1482
Current measuring
range exceeded
1523
Device error
1605
Supply voltage
missing
1755
Overtemperature of
electronic
components
Visible on the display of the 3RW5 HMI Standard.
1)
Acknowledgment via Manual RESET.
2)
Acknowledgment via Remote RESET.
3)
Acknowledgment via Auto RESET.
4)
Acknowledgment depends on parameter RESET MODE.
5)
SIRIUS 3RW50 soft starter
Manual, 09/2019, A5E35628455002A/RS-AA/001
Cause
Error appears without
motor start:
Motor incorrectly
connected
Inside-delta circuit
wrongly configured
Ground fault
Error appears while
motor is starting:
Starting voltage too
high
With sensors: The
measured value
exceeds the measuring
range
With actuators: The
output value exceeds a
high limit value
Unrecoverable error
detected after internal
diagnostics (self-test,
contactor contacts,
switching element, etc.).
The line side switch or
the power supply is not
plugged in correctly.
No current
The temperature in the
components has exceeded
the maximum limit.
8.4 Faults and remedial actions of the 3RW50 soft starter
Remedy
Check and correct the
wiring.
Adapt parameters.
Check the interaction
between the module and
the sensor or actuator.
Replace the device.
Please contact Technical
Support (Support
Request (Page 37)).
Check the cables and the
cable connections and
replace any defective
components.
Check the ambient
temperature or the control
cabinet ventilation.
Messages and diagnosis
RESET MODE
Manual
Remote
Auto
2)
3)
x
x
-
x
x
-
-
-
-
x
x
-
-
-
x
4)
171