Setting Parameterizing Mode Via Key Combination On The 3Rw50 Soft Starter; Activate Parameterizing Mode - Siemens SIRIUS 3RW50 Manual

Industrial controls, soft starters and semiconductor switching devices
Table of Contents

Advertisement

5.8
Setting parameterizing mode via key combination on the
3RW50 soft starter
5.8.1

Activate parameterizing mode

Adjustable parameters in parameterizing mode
● Control via digital input (Page 139)
● Output 13 / 14 (ON / RUN) (Page 99)
Requirements
During the activation you must be able to switch off the supply voltage.
Procedure
1. Press the MODE key during operation longer than 2 seconds until the
STATE / OVERLOAD LED flickers green and press and hold the MODE key.
2. Switch off the supply voltage of the 3RW50 soft starter for at least 5 s. After the 5 s
elapse, you can release the MODE key.
3. Press and hold the MODE and TEST / RESET keys.
4. Switch the supply voltage of the 3RW50 soft starter on again.
When the SOFT TORQUE and RESET MODE LEDs flicker green, the parameterization
mode is active. You can release the MODE and TEST / RESET keys.
Result
You have activated the parameterizing mode and can now set the parameters (Page 102).
Further parameterization options
● 3RW5 HMI High Feature
Menu: "Parameters > Soft Starter > Additional parameters > Control via digital input"
Menu: "Parameters > Soft Starter > ON / RUN relay output"
● Parameterizing output 13 / 14 (output signal ON or RUN) (Page 99)
SIRIUS 3RW50 soft starter
Manual, 09/2019, A5E35628455002A/RS-AA/001

5.8 Setting parameterizing mode via key combination on the 3RW50 soft starter

Parameter assignment
101

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents