Micro Sd Card - Siemens SIRIUS 3RW50 Manual

Industrial controls, soft starters and semiconductor switching devices
Table of Contents

Advertisement

7.12.4

Micro SD card

Operating principle
In combination with a micro SD card, the 3RW5 HMI High Feature can perform firmware
updates, exchange configuration files and service data, and store logbooks.
The replacing of configuration files allows serial parameter assignment
(3RW5 HMI High Feature and 3RW5 communication module) and supports the device
replacement. Observe the respective transferred parameters and data in this regard.
Requirements
● Inserted micro SD card, e.g. micro SDHC Class 10
– File format: FAT32
– Capacity: max. 32 GB
● 3RW5 HMI High Feature
Menu: "Micro SD card"
The "Micro SD card" menu is only visible after you have inserted a micro SD card into the
3RW5 HMI High Feature.
● Access protection to the 3RW5 HMI High Feature is not active or has been reset.
● Load data onto the 3RW50 soft starter ("Load communication and HMI parameters to
soft starter" or "Device change"):
– Make sure that there is only 1 folder with configuration data on the micro SD card.
– Rename the folder as follows: "1P3RW5 xxx-xxx" (specify the article number of the
SIRIUS 3RW50 soft starter
Manual, 09/2019, A5E35628455002A/RS-AA/001
3RW50 soft starter instead of the placeholders "x".)
Example: When you use a soft starter of size S6 with article number
"3RW5055-2AB04", name the folder as follows: "1P3RW5 055-2AB".