Siemens SIRIUS 3RW50 Manual page 135

Industrial controls, soft starters and semiconductor switching devices
Table of Contents

Advertisement

Observing standards
Increased danger in hazardous areas means it is necessary to carefully observe the
following standards:
● IEC / EN 60079-14 / VDE 0165-1: For electrical apparatus for hazardous areas.
● IEC / EN 60079-17: Inspection and maintenance of electrical installations in explosive
atmosphere.
● EN 50495: Safety devices required for the safe functioning of equipment with respect to
explosion risks.
ATEX / IECEx-specific safety data
The motor protection function according to ATEX / IECEx for 3RW50 soft starters has the
following safety data:
● Safety Integrity Level (SILCL): 1
● Hardware Fault Tolerance (HFT): 0
● Interval for testing the protective functions: 3 years
● Probability of failure on demand (PFD): 8x10-3
● Probability of a dangerous failure per hour (PFH): 5x10-7 1/h
Maintenance and repair
The 3RW50 soft starters are maintenance-free. The repair of soft starters with approval
according to IEC 61508 / EN 13849 is only permissible in the manufacturer's plant.
A repair on 3RW50 soft starters that is not performed in the manufacturer's plant results in
loss of ATEX / IECEx approval.
SIRIUS 3RW50 soft starter
Manual, 09/2019, A5E35628455002A/RS-AA/001
7.7 ATEX / IECEx-certified motor overload protection
Functions
135