SIRIUS 3RW52 Soft Starter Siemens Industry Online Support Safety information Description Industrial Controls Mounting and dismantling Soft starters and solid-state switching devices Wiring SIRIUS 3RW52 Soft Starter Parameter assignment Equipment Manual Commissioning Functions Messages and diagnostics Maintenance and servicing Technical specifications...
Page 2
Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
Table of contents Siemens Industry Online Support ......................9 Support Request ........................12 Additional documentation ....................... 13 Safety information ..........................15 ESD Guidelines ........................15 Five safety rules for working in or on electrical systems ............17 Reactive power compensation ....................18 Electromagnetic compatibility (EMC) according to IEC 60947-4-1 ........
Page 4
Design and operator controls of the High Feature 3RW5 HMI ..........111 6.10 Menu of the 3RW5 HMI High Feature ................. 113 6.11 Parameterize analog output AQ via the 3RW5 HMI High Feature ........121 SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 5
Diagnostics options ....................... 169 LED display ........................... 170 9.2.1 Overview of the device LEDs of the 3RW52 soft starter ............170 9.2.2 Status and error displays ...................... 171 9.2.3 STATE / OVERLOAD LED ....................172 SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 6
Device change with micro SD card on the 3RW5 HMI High Feature ........205 10.5.2 Device change with SIRIUS Soft Starter ES (TIA Portal) ............ 206 Technical specifications ........................207 11.1 Technical data in Siemens Industry Online Support ............207 Dimension drawings ..........................209 12.1 CAx data ..........................209 12.2 Drilling pattern for 3RW5 HMI Standard ................
Page 7
EMERGENCY STOP shutdown to SIL 3 or PL e with a 3SK1 safety relay ......242 A.3.5 Contactor for emergency start ....................247 Third-party software ..........................249 Information about third-party software .................. 249 Glossary ............................. 253 Index..............................255 SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Siemens Industry Online Support Information and service At Siemens Industry Online Support you can obtain up-to-date information from our global support database: Product support Application examples Forum mySupport Link: Siemens Industry Online Support (https://support.industry.siemens.com/cs/ww/en) Product support You can find information and comprehensive know-how covering all aspects of your product...
Page 10
Configure your individual documentation from different manuals. CAx data Easy access to CAx data, e.g. 3D models, 2D dimension drawings, EPLAN macros, device circuit diagrams My IBase registrations Register your Siemens products, systems and software. SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 11
Siemens Industry Online Support Siemens Industry Online Support app The Siemens Industry Online Support app provides you access to all the device-specific information available on the Siemens Industry Online Support portal for a particular article number, such as operating instructions, manuals, data sheets, FAQs etc.
Siemens Industry Online Support 1.1 Support Request Support Request Use the Support Request online form to send your question directly to Technical Support: Support Request: Internet (https://support.industry.siemens.com/My/ww/en/requests) SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
(https://support.industry.siemens.com/cs/ww/en/view/109758201) Online help for SIRIUS Soft Starter ES (TIA Portal) Online help for STEP 7 The EMC Directive 2014/30/EU in practice (http://www.siemens.com/emc-guideline) Industrial Control Panels and Electronic Equipment of Industrial Machinery for North America (http://www.siemens.com/UL508A) Control Panels compliant with IEC Standards and European Directives (http://www.siemens.com/iec60204)
Page 14
Siemens Industry Online Support 1.2 Additional documentation Interesting links Manuals in Siemens Industry Online Support (https://support.industry.siemens.com/cs/ww/en/ps/man) FAQs for soft starters 3RW5 (https://support.industry.siemens.com/cs/ww/en/ps/16212/faq) Downloads for soft starters 3RW5 (https://support.industry.siemens.com/cs/ww/en/ps/16212/dl) Catalog IC 10 (https://support.industry.siemens.com/cs/ww/en/view/109747945) Product support for STEP 7 (TIA Portal) (https://support.industry.siemens.com/cs/ww/en/ps/14672) Premium Efficiency - Efficiency class IE3 (http://w3.siemens.com/mcms/topics/en/application-...
The damage caused to a device by overvoltage is usually not immediately evident and is only noticed after an extended period of operation. SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 16
PCB traces. In this way, the discharged energy cannot reach or damage sensitive devices. Discharge your body before taking any necessary measurements on a device. Do so by touching grounded metallic parts. Use only grounded measuring instruments. SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
5. These parts should be covered, or barriers erected around them, to avoid accidental contact during the work with adjacent parts that are still live. SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
3RW5 soft starter, the capacitors must be disconnected from the 3RW5 soft starter when the contactor is open. You will find further information in the Internet (https://support.industry.siemens.com/cs/ww/en/view/67131557). SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Electromagnetic compatibility (EMC) according to IEC 60947-4-1 This product is designed for Environment A. It may produce radio interference in domestic environments, in which case the user may be required to take adequate mitigation measures. SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Siemens’ products and solutions undergo continuous development to make them more secure. Siemens strongly recommends that product updates are applied as soon as they are available and that the latest product versions are used. Use of product versions that are no longer supported, and failure to apply the latest updates may increase customer’s exposure...
Protect freely accessible operator controls on your machine / system against unauthorized actuation if this could result in a risk or danger. Take suitable action in this regard, for example, a lockable key-operated switch. SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
3RW52 soft starter 3RW5 HMI High Feature (accessory) 3RW5 communication module (accessory) You will find current downloads and a history of the versions with new features on the 3RW5 topic page (https://support.industry.siemens.com/cs/ww/en/view/109747404). SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
For environmentally friendly recycling and disposal of your old device, please contact a company certified for the disposal of old electrical and/or electronic devices and dispose of the device in accordance with the regulations in your country. SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 24
Safety information 2.8 Recycling and disposal SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Commissioning Service and maintenance Requirements for use of 3RW5 soft starters Basic knowledge of the following areas: General electrical engineering Drive technology Automation technology Handling the automation system and the software used SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Revision of the manual Addition of functions for the 3RW52 soft starter (e.g. response to bus error / control via digital input, restoration of factory settings with the keys MODE and RESET / TEST) SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
You will also find the applicable scale in the Technical data (Page 207). Diagnostics LEDs and RESET / TEST key Eye for lead seal Main circuit connection (motor) Control terminals (inputs/outputs) Control cable duct with cover SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Set starting voltage Rated operating speed n reached Rated operational voltage End of the set ramp up time Rated operating speed of the motor Switch-on command is cancelled, motor is switched off SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 29
You will find an overview of all of the functions of the 3RW5 soft starter in the Catalog IC 10 (https://support.industry.siemens.com/cs/ww/en/view/109747945). You will find further details of the functions in chapter Functions (Page 131). SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Description 3.5 Access options for the 3RW52 soft starter Access options for the 3RW52 soft starter SIRIUS 3RW52 soft starter LED display on 3RW52 soft starter Fieldbus (via optional communication module) PC or programming device with configuration software of the controller, e.g. STEP 7 Programmable logic controller, e.g.
Page 31
Analog output (for device version with analog output only) and ON / RUN relay output can be set. Communication parameters of all compatible communication modules can be set. Station address can be set for a 3RW5 PROFIBUS and Modbus RTU communication module. SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Control source: SIRIUS Soft Starter ES (TIA Portal) Premium / Professional, operating mode: Manual - bus Control source: SIRIUS Soft Starter ES (TIA Portal), operating mode: Manual operation local - PC controlled SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 33
Professional Manual - local Input controlled Input IN 3RW5 HMI controls 3RW5 HMI PC controlled SIRIUS Soft Starter ES (TIA Portal) Highest Explanation in text below Lowest priority without 3RW5 communication module SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 34
Operating mode "manual - local": Control switches to "Manual - local - Input controlled". Additional information You will find further information on the 3RW5 communication modules in the manual for the 3RW5 communication module used. SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Brief overview: Window "Task Card" > Tab "Online Tools" > "SIRIUS Control Panel > Master Control > Release Control" Withdrawal of master control by other control sources In "Automatic" mode, control can be withdrawn by any control source. SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 36
Command in SIRIUS Soft Starter ES (TIA Portal) (local interface on the 3RW5 HMI High Feature) Brief overview: Window "Task Card" > Tab "Online Tools" > "SIRIUS Control Panel > Master Control > Get Control" SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 37
Command in SIRIUS Soft Starter ES (TIA Portal) (local interface on the 3RW5 HMI High Feature) Brief overview: Window "Task Card" > Tab "Online Tools" > "SIRIUS Control Panel > Master Control > Get Control" SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 38
3RW5 HMI High Feature, master control is taken from the 3RW5 HMI. Brief overview: Window "Task Card" > Tab "Online Tools" > "SIRIUS Control Panel > Master Control > Get Control" SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 39
You will find more information on the process images and data tables in the manual for the 3RW5 communication module in question. Further information on the operation of SIRIUS Soft Starter ES (TIA Portal) can be found in the online help of SIRIUS Soft Starter ES (TIA Portal). SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 41
The stated power ratings apply to a rated operational voltage of U = 400 V in an inline circuit. Size 1 Size 2 Size 3 Size 4 Rated operational current Rated power SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
No pressure surges, e.g. for pumps Increased service life of the pipe system, e.g. for compressors Reduced starting current, e.g. for agitators Reduced stress on gearbox and V belt, e.g. for saws SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
You can download the Simulation Tool for Soft Starters (STS) for free on the 3RW5 topic page (https://support.industry.siemens.com/cs/ww/en/view/109747404). SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Rated control supply voltage U 24 V AC/DC 110 V - 250 V AC Rated operational voltage U 200 - 480 V AC 200 - 600 V AC Explanation in the following table. SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 45
= 110 kW = 250 A = 132 kW = 315 A = 160 kW = 370 A = 200 kW = 470 A = 250 kW = 570 A = 315 kW SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
The 3RW52 soft starter can be integrated in an automation software, e.g. STEP 7 (TIA Portal) via GSD / GSDML or HSP. You will find further information on operation of the 3RW5 communication module in the Manual for the 3RW5 communication module in question. SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
(TIA Portal) provides reliable information, which helps you to avoid faults, or quickly locate and eliminate faults if they occur. Illustration similar Download You can download SIRIUS Soft Starter ES (TIA Portal) via the following link (https://support.industry.siemens.com/cs/ww/en/ps/24231/dl). SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 50
The "Professional" variant corresponds to the "Premium" version of V15.1 Additional information You will find further information on SIRIUS Soft Starter ES (TIA Portal) and necessary versions and updates in Catalog IC 10 (https://support.industry.siemens.com/cs/ww/en/view/109747945) and on the 3RW5 topic page (https://support.industry.siemens.com/cs/ww/en/view/109747404). SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Display of the device LEDs of the 3RW5 HMI Standard shows the messages of the following devices: – 3RW52 soft starter – 3RW5 HMI Standard – Communication module (if there is one) SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 52
SD card for the following devices: – 3RW52 soft starter – 3RW5 HMI High Feature – Communication module (if there is one) Note the information in chapter Firmware update (Page 22). SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
2. Mount the 3RW52 soft starter on a level surface (Page 56). 3. Ensure that the permissible temperature range and the necessary clearances are complied with. Technical data in Siemens Industry Online Support (Page 207) 4. Optionally install the 3RW5 HMI Standard (accessory) or 3RW5 HMI High Feature (accessory).
3RW523.-..Size 4 3RW524.-..3RW5984-0FC00 Please observe the following notice. Note 3RW52 soft starter without fan The following 3RW52 soft starters do not require a fan cover: 3RW5213-..3RW5214-..3RW5215-..3RW5224-..3RW5225-..SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 55
– Size 4: You require 1 fan cover and 4 of the screws packed with the product. Result The fan cover provides enhanced touch protection and prevents the fan from being blocked by foreign objects. SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Article number Screws Tightening torque Size 1 3RW521.-..5 Nm Size 2 3RW522.-..Size 3 3RW523.-..Size 4 3RW524.-..8 Nm The following figure shows the minimum clearances for the 3RW52 soft starter: SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 57
Tilt the 3RW52 soft starter up so that it is resting level against the mounting plate tighten all 4 screws with the specified torque Result You have mounted the 3RW52 soft starter on a level surface and can now connect (Page 81) it. SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Make sure that the locking switch on the rear of the 3RW5 HMI Standard is in the required position. You will find further information in chapter Standard 3RW5 HMI (Page 149). Observe the coding of the plug and socket Lock the connector in the socket SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 59
Cable routing to the left Replace the hinged cover of the 3RW52 soft starter as required. (Page 76) Result You have installed the 3RW5 HMI Standard in the 3RW52 soft starter and can commission it. SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
You have removed the 3RW5 HMI Standard. You can install the 3RW5 Standard on a surface (Page 71) or in a cabinet door (Page 63) or you can install a new 3RW5 HMI Standard (Page 58). SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Replace the hinged cover of the 3RW52 soft starter as required. (Page 76) Result You have installed the 3RW5 HMI High Feature in the 3RW52 soft starter and can commission it (Page 129). SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
You have removed the 3RW5 HMI High Feature. You can install the 3RW5 HMI High Feature on a surface (Page 73) or in a cabinet door (Page 67) or you can install a new 3RW5 HMI High Feature (Page 61). SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Procedure without door mounting kit IP65 Place the 3RW5 HMI Standard in the cutout of the control cabinet door . Ensure that the 3RW5 HMI Standard engages audibly in the 4 fixtures SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 64
10 mm at the front. Fasten the fixing brackets onto the 3RW5 HMI Standard Tighten the 3RW5 HMI Standard with a tightening torque of 0.3 ... 0.35 Nm Ensure that all of the screw heads are in contact with the fixing bracket. SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 65
Make sure that you install the cable in accordance with EMC requirements. For example, install data cables separately from the motor cable. Connect both sides of shielded cables over a large surface area. SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 66
Connect both sides of shielded cables over a large surface area. Result You have installed the 3RW5 HMI Standard in the cabinet door and can commission it. SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Procedure without door mounting kit IP65 Place the 3RW5 HMI High Feature in the cutout of the control cabinet door . Ensure that the 3RW5 HMI High Feature engages audibly in the 4 fixtures SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 68
Fasten the fixing brackets onto the 3RW5 HMI High Feature Tighten the 3RW5 HMI High Feature with a tightening torque of 0.3 ... 0.35 Nm Ensure that all of the screw heads are in contact with the fixing bracket. SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 69
Make sure that you install the cable in accordance with EMC requirements. For example, install data cables separately from the motor cable. Connect both sides of shielded cables over a large surface area. SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 70
Connect both sides of shielded cables over a large surface area. Result You have installed the 3RW5 HMI High Feature in the cabinet door and can commission it (Page 129). SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Make sure that you install the cable in accordance with EMC requirements. For example, install data cables separately from the motor cable. Connect both sides of shielded cables over a large surface area. SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 72
Insert the push-in lugs into each side of the enclosure until you hear them engage fix the 3RW5 HMI Standard on the wall Result You have installed the 3RW5 HMI Standard on a flat surface and can commission it. SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Make sure that you install the cable in accordance with EMC requirements. For example, install data cables separately from the motor cable. Connect both sides of shielded cables over a large surface area. SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 74
Insert the push-in lugs into each side of the enclosure until you hear them engage fix the 3RW5 HMI High Feature on the wall Result You have installed the 3RW5 HMI High Feature on a flat surface and can commission it (Page 129). SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
You have cut out the hinged cover for a 3RW5 HMI and can installed a 3RW5 HMI High Feature (Page 61) or 3RW5 HMI Standard (Page 58) in the 3RW52 soft starter. SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Loosen the hinges vertical to the soft starter surface starting from the bottom. Take the cover off the 3RW52 soft starter. Follow the steps in reverse order to install the replacement hinged cover. SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
(optional, average phase current in %) AQ- / AQ U+: For signal type voltage, signal range 0 ... 10 V AQ- / AQ I+: For signal type current, signal range 4 - 20 mA (factory setting) SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 78
13, 14 (ON / RUN) (Page 108). Note Parameterizing the analog output You can parameterize the output of the analog output with the 3RW5 HMI High Feature (Page 121). SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Wiring 5.1 Connections 5.1.2 State diagrams of the inputs and outputs SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 80
Output 13, 14 (output 1): Parameterized to signal operating state RUN Output 23, 24 (output 2): To signal operating state BYPASSED Output 95, 96 (NC) (output 3): For signaling faults Output 95, 98 (NO) (output 3): For signaling faults Temperature sensor (Thermoclick) SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
– Connecting the control terminals (spring-type terminals) (Page 90) 4. Mount the supplied cover for the control cable duct (Page 94). Result The 3RW52 soft starter is connected and ready to operate. SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Terminal cover (accessory) for 3RW52 soft starter (sizes 2, 3, and 4) Note Touch protection by terminal cover. Touch protection according to EN 50274 finger-safe only for vertical contact from the front. SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 85
Illustration similar Make sure that you mount the terminal cover the right way round, as shown in the diagram. If you have to remove the terminal cover, proceed in the reverse order. SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Turn off and lock out all power supplying this device before working on this device. Illustration similar Pry the box terminal block off the main circuit connections Pull the box terminal block off the main circuit connections SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 87
Wiring 5.5 Replacement of the box terminal blocks with size 2 Assembly procedure Illustration similar Plug the new box terminal block into the main circuit connections SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Control by PLC (Page 226) Actuation of a line contactor (Page 228) Wiring for remote RESET (Page 230) Connecting the temperature sensor (Page 231) Connecting the evaluation unit to the analog output (Page 232) SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Pay attention to the required tools indicated on the front of the 3RW52 soft starter beneath the hinged cover. Procedure DANGER Hazardous voltage. Will cause death or serious injury. Turn off and lock out all power supplying this device before working on this device. Illustration similar SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Control by PLC (Page 226) Actuation of a line contactor (Page 228) Wiring for remote RESET (Page 230) Connecting the temperature sensor (Page 231) Connecting the evaluation unit to the analog output (Page 232) SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Pay attention to the required tools indicated on the front of the 3RW52 soft starter beneath the hinged cover. Procedure DANGER Hazardous voltage. Will cause death or serious injury. Turn off and lock out all power supplying this device before working on this device. Illustration similar SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Will cause death or serious injury. Turn off and lock out all power supplying this device before working on this device. Illustration similar Press against the lock and pull the control terminal out SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 93
Wiring 5.10 Replacing the control terminals Assembly procedure Illustration similar Place the control terminal onto the intended connection until the terminal engages. SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Lay the control cables in the control cable ducts and fix the control cables in place with cable ties. Press the cover for the control cable duct into the openings provided until it audibly engages SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Procedure Illustration similar Press the cover of the control cable channel at top and bottom from the front and remove the cover for the control cable channel of the 3RW52 soft starter SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 96
Wiring 5.12 Removing the cover of the control cable duct SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
CLASS setting for the motor overload protection Rated operational current I of the motor Current limiting factor as a multiple of the set rated operational current I of the motor Ramp up time Starting voltage Stopping time SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 98
Flat-bladed screwdriver or cross-tip screwdriver PZ1 Procedure Insert the flat-bladed screwdriver in the opening of the setting element. Turn the flat-bladed screwdriver until the arrow of the setting element points to the required parameter setting. SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 99
Display of the parameter values in SIRIUS Soft Starter ES (TIA Portal) Brief overview: Window "Project Navigation" with current project under created Soft Starter > "Parameters" > Window "Work area" > "Soft Starter > Parameter list" SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
20% from the rating plate specification of the manufacturer. For meaning of scale, refer to the laser-inscribed table on front panel of device or in the Technical Data. SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
4 × I Hydraulic pump 4 × I Not relevant Agitator 4 × I Not relevant Milling machine 4 × I Not relevant It is recommended that the "Soft torque" function is activated. SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Result The 3RW52 soft starter has been parameterized and is ready to operate. You can parameterize the signal of the analog output via a 3RW5 HMI High Feature (accessory) (Page 121). SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Reset the start command (e.g. via the PLC or switch) before performing a reset. To do this, for example, link the group error output (terminals 95 and 96) into the control. SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 104
Manual RESET Remote RESET Flashes green Auto RESET Lights up green Soft torque You will find further information in chapter Soft Torque (Page 141). Soft Torque LED Set soft torque Lights up green SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
(control supply voltage) off and on again. The power supply (control supply voltage) on the 3RW52 soft starter must be switched off for at least 4 seconds. Auto RESET "Auto RESET" means that faults are automatically reset as soon as the cause is eliminated. SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Supply voltage (control supply voltage) is present. The 3RW52 soft starter does not signal any faults, the LED STATE / OVERLOAD is off. Video instructions Video instructions can be found in SIOS (https://support.industry.siemens.com/cs/ww/en/view/109778873): SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 107
3RW5 HMI High Feature (accessory) Menu: "Parameters > Soft Starter > ON / RUN relay output" Procedure in chapter Parameterize the response to bus errors and output 13, 14 (ON / RUN) (Page 108) SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
You can recognize your selection by the color of the STATE / OVERLOAD LED. Parameters to be changed STATE / OVERLOAD No selection Control via digital input Lights up green Output ON / RUN Lights up red SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 109
(3RW5 HMI High Feature with firmware version V3.0 and higher) – Menu: "Parameters > Soft Starter > ON / RUN relay output" Procedure in chapter Parameterize output 13, 14 (output signal ON or RUN) (Page 106) SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 110
You will find further information on output 13, 14 in chapter Parameterize output 13, 14 (output signal ON or RUN) (Page 106). You will find further information on parameter "Control via digital input" in chapter Response to bus errors / Control via digital input (Page 147). SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Eyes for lead seals Hole for mounting the interface cover Status LED (Page 174) Local interface (point-to-point connection between PC and 3RW5 HMI High Feature) Slot for micro SD card (Page 166) SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 112
If you confirm the information with the OK key, the 3RW5 HMI High Feature fetches control (Local). To execute the function, you must then enter it again. Refer to chapter Operating modes and master control function (Page 32). SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Only visible if a micro SD card is inserted. Additional information Menu item "Additional information" shows the following QR code. The link behind the QR code is the 3RW5 topic page (https://support.industry.siemens.com/cs/ww/en/view/109747404). SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 114
3RW5 HMI High Feature firmware version V3.0 or higher Further menu items. Refer to chapter Monitoring the process image of the 3RW52 soft starter with the High Feature 3RW5 HMI (Page 158). SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 115
6.10 Menu of the 3RW5 HMI High Feature Further menu items. Refer to chapter Diagnostics of the 3RW52 soft starter with the 3RW5 HMI High Feature (Page 182). 3RW5 HMI High Feature firmware version V2.0 or higher SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 116
Parameter assignment 6.10 Menu of the 3RW5 HMI High Feature SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 117
3RW5 HMI High Feature firmware version V2.0 or higher 3RW5 HMI High Feature firmware version V3.0 or higher For 3RW5 PROFINET Standard communication module For 3RW5 EtherNet/IP communication module For 3RW5 Modbus TCP communication module SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 118
Display depends on the current setting Further menu items. Refer to chapter Monitoring the measured values of the 3RW52 soft starter with the 3RW5 HMI High Feature (Page 154). Contains the lower level with settable languages. SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 119
Parameter assignment 6.10 Menu of the 3RW5 HMI High Feature SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 120
6.10 Menu of the 3RW5 HMI High Feature Display depends on the current setting 3RW5 HMI High Feature firmware version V3.0 or higher 3RW5 HMI High Feature firmware version V2.0 or higher SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Menu: "Parameters > Soft Starter > Analog output" Access protection to 3RW5 HMI High Feature is not active or has been reset Device version with analog output Evaluation unit is connected properly (Page 232). SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 122
2. Parameterize the range start value and the range end value taking the following factor into account: – Range start value (e.g. 50% / 3.125%) – Range end value (e.g. 200% / 3.125%) SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 123
PLC. Make sure that the analog input of the PLC is not connected to the supply voltage (control supply voltage) of the 3RW52 soft starter and is floating. You will find further information in the application example in the FAQs (https://support.industry.siemens.com/cs/ww/en/view/109778700). SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
If no keys on the 3RW5 HMI High Feature are pressed, the display will shut down after a specified time period has elapsed. The setting "0 min" deactivates shutdown of the display. Factory setting: 5 min Setting range: 0 ... 60 min Increment: 1 min SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 125
Languages The required language is set in the "Languages" menu. English (factory setting) German French Spanish Italian Portuguese Chinese Additional language (Page 168) Only visible if an additional language has been added. SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Note the information in chapter Micro SD card (Page 166). 7. If you wish, repeat the procedure for further 3RW5 HMI High Features. Result You have parameterized several 3RW5 HMI High Features identically on different 3RW52 soft starters. SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
The 3RW52 soft starter is ready for operation and protected from external access. You will find additional information on operating modes and the respective control priority in chapter Operating modes and master control function (Page 32). SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
SD card from unauthorized access. Proceed in the same sequence as for sealing the hinged cover. You will find further information in chapter Design and operator controls of the High Feature 3RW5 HMI (Page 111). SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
The 3RW5 HMI High Feature is ready to use. You will find an overview of the functions in chapter 3RW5 HMI (Page 51). Note the menu structure in chapter Menu of the 3RW5 HMI High Feature (Page 113). SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 130
Commissioning 7.3 First commissioning of the High Feature 3RW5 HMI SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
E.g. pumps or small fans Voltage characteristic Voltage ramp with short ramp up time t Voltage ramp with long ramp up time t Line voltage Parameterizable starting voltage Short ramp up time Long ramp up time SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 132
Current characteristic with direct-on-line starting without 3RW52 soft starter Current characteristic with short ramp up time Current characteristic with long ramp up time Rated operational current Rated operating speed of the motor SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 133
With the setting "0 s", the motor is switched on with a ramp up time of approx. 100 ms. Factory setting: 10 s Setting range: 0 ... 20 s SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
3RW52 soft starter has detected the motor ramp up and the motor is in a normal operating state. Application Avoiding current surges Reducing energy costs Current path Current characteristic with direct-on-line starting without 3RW52 soft starter Adjustable current limiting value Voltage ramp Rated operational current during rated operation SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 135
= 7 x 47 A = 329 A You will find the scale of the setting element I on the front of the 3RW52 soft starter under the hinged cover and in the Technical Data (Page 207). SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
The setting "0 s" causes the motor to be shut down immediately without a down ramp. Factory setting: 0 s Setting range: 0 ... 20 s SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Damage to property possible due to deactivated motor protection. If the motor is not monitored by a temperature sensor and the trip class is set to "CLASS OFF", no motor protection is provided. SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 138
Manual RESET or Remote RESET set, a RESET is only possible once the recovery time has elapsed. You will find further information on resetting the faults in chapter RESET MODE (Page 105). SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
You will find further information on resetting the faults in chapter RESET MODE (Page 105). You will find more information on the connection of the temperature sensor in chapter Connecting the temperature sensor (Page 231). SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
(recovery time) prior to acknowledging the fault or restarting the motor. In the event of power semiconductor overload: 30 s In the case of bypass overload: 60 s SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Torque curve Torque with direct-on-line starting Torque without Soft torque Torque with Soft torque SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 142
3 seconds is set. Speed curve Rated operating speed of the motor Motor speed with Soft torque Motor speed without Soft torque SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
The parameter defines how the master control behaves on failure of the bus connection or a CPU stop. For more setting options and further information, see chapter Response to bus errors / Control via digital input (Page 147). SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Brief overview: See SIRIUS Soft Starter ES (TIA Portal) via the local interface on the 3RW5 HMI High Feature – Configuration software of the control system (e.g. STEP 7 with corresponding HSP) – User program SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
3RW5 HMI High Feature (accessory) with firmware version V3.0 or higher Access protection to 3RW5 HMI High Feature is not active or has been reset. Menu: "Parameters > Soft Starter > Additional parameters > Control via digital input" SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 148
3RW5 communication module in question. You will find further information on removal of the 3RW5 communication module in the manual of the relevant 3RW5 communication module. SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Design of the Standard 3RW5 HMI Display Navigation keys RESET / TEST Status LED (Page 173) Device LEDs (Page 173) Plug-in connection for HMI connecting cable Locking switch Cable duct Start key Stop key LOCL/REMT SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 150
3RW5 HMI Standard is in the "Locked" switch position, the "RESET / TEST", "LOCL/REMT" and "Start" and "Stop" keys are disabled. Navigation through the menu using the navigation keys, however, is still possible. SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
(thermal model of the semiconductor). S-TRQ (Soft torque) The Soft torque function is activated. S-TRQ The Soft torque function is deactivated. S-TRQ SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 152
Remote RESET Station address for PROFIBUS PBADR (only displayed if a 3RW5 PROFIBUS communication module is used) Station address for Modbus MODBS (only displayed if a 3RW5 Modbus RTU communication module is used) SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 153
4. To exit the menu, press and hold a navigation key until the entry "ERROR" appears on the display. Alternatively, the 3RW5 HMI Standard automatically exits the menu after 5 seconds of inactivity. SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Brief overview: See SIRIUS Soft Starter ES (TIA Portal) via the local interface on the 3RW5 HMI High Feature – Configuration software of the control system (e.g. STEP 7 with corresponding HSP) – User program SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 155
Switching element heating The currently calculated switching element heating is continuously compared with the previously saved switching element heating and indicated in %. 3RW5 HMI High Feature firmware version V3.0 or higher SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
3. Press the ESC key to exit the bar chart view. The example chart shows the current 3 phase currents (L1/L2/L3) and the associated average value as a percentage. The scaling of the x-axis is 200%. SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 157
The sample chart shows the current phase current I IL1 as a percentage. The scaling of the y-axis is 200%. If the measured value exceeds the limit of the scaling (200% in the example), the line extends parallel with the x-axis and is displayed red in that area. SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
– Configuration software of the control system (e.g. STEP 7 with corresponding HSP) – User program Additional information You will find further information on transferring the process images via a fieldbus in the device manual for the respective 3RW5 communication module. SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 159
Float32 Phase current IL3 (rms) Process image output (PIQ) Process data Process image DQ 0.0 Motor CW DQ 0.3 Reset DQ 0.5 Self-test (user-test) DQ 3.0 Manual operation local - input controlled SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
(slot 0) has adjustable and readable I&M1, I&M2 and I&M3 data. The "Station" comprises the following devices: 3RW5 communication module (slot 1) 3RW5 soft starter (slot 2) 3RW5 HMI High Feature (slot 3) SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 161
Module Article number (if existing) Hardware Firmware Manufacturer information Manufacturer Serial number Part of the I&M0 data Part of the I&M1 data Part of the I&M2 data Part of the I&M3 data SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Menu entry is displayed if a PIN has been defined. Menu entry is displayed after logging off with an active PIN. Menu entry is displayed after logging on with an active PIN. SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
3RW5 HMI High Feature. Confirm by pressing the OK key. The 3RW5 HMI High Feature then returns to the "Local access protection" menu. Result You have defined the PIN and the set PIN is active. SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
If the entry is correct, the user information "Log on was successful" appears on the display of the 3RW5 HMI High Feature. Confirm by pressing the OK key. Result You have changed the PIN and the changed PIN is active. SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
You can reset the local access protection to the factory setting with the master RESET key on the rear of the 3RW5 HMI High Feature (Page 202). Result You have deactivated and deleted the current PIN. SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
I&M 1 data (Page 160) I&M 3 data (Page 160) Device parameters of the 3RW5 HMI High Feature Communication parameters Applications: Parameterize 3RW5 HMI High Feature serially / identically (Page 126) "Device change" function (Page 204) SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 167
The memory capacity is displayed. Complete memory Free memory Used memory 3RW52 Soft Starter from firmware version V2.0 3RW5 HMI High Feature firmware version V2.0 or higher 3RW5 HMI High Feature firmware version V3.0 or higher SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
2. Select the required language file on the micro SD card and confirm with OK. Result You have loaded an additional language onto the 3RW5 HMI High Feature and can set it with the selection "Additional language" (Page 124). SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Soft Starter > "Commissioning" > Window "Work area" > "Soft Starter / HMI > Diagnosis" Further diagnostics options You will find further diagnostics options via the fieldbus in the manual for the respective 3RW5 communication module. SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
At least one warning exists. The cause has not been eliminated. Lights up yellow LED combinations State Meaning The 3RW52 soft starter is not ready for operation. Device error detected Flashes Flashes Flashes green yellow SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Motor has decelerated to zero speed and shut down due to overload error an overload error. Flashes red A motor overload error exists, e.g.: Motor is too hot Temperature sensor wire break Temperature sensor short circuit SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
You will find more information on the messages of the 3RW52 soft starter in the chapter Status and error displays (Page 171). You will find further information on the messages of the 3RW5 communication module in the manual for the 3RW5 communication module in question. SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
You will find more information on the messages of the 3RW52 soft starter in the chapter Status and error displays (Page 171). You will find further information on the messages of the 3RW5 communication module in the manual for the 3RW5 communication module in question. SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Internal fan is dirty (not rotating freely). Check the function of the fan. Connecting cable has fallen off or is Clean the fan. defective. Check the wiring. Internal fan faulty Replace the fan. SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Check the ambient overload (switch contact, power conditions associated with semiconductors) too hot. cooling. You may want to consider lowering the operating characteristics. Check the number of switching operations. Acknowledgment after cooling down SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 177
Execute a complete and / or the firmware firmware update. expansions are incomplete Check any error or incompatible. messages that occur. Check to see whether or not the firmware update has been interrupted. SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 178
L2 and L3 and replace defective bypasses. 1418 Bypass protective An excessively high current Check the motor. shutoff has occurred in bypass Check the dimensioning of mode. the soft starter. Acknowledgment after cooling down SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 179
Check the interaction With sensors: The range exceeded between the module and the measured value has sensor or actuator. exceeded the range limits. With actuators: The output value has exceeded an upper limit. SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 180
Visible on the display of the 3RW5 HMI Standard. Acknowledgment via Manual RESET. Acknowledgment via Remote RESET. Acknowledgment via Auto RESET. Acknowledgment depends on parameter RESET MODE. SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Check any error messages that occur. the loaded language is language' Check to see whether or not loading the incomplete or incompatible. language has been interrupted. 3RW5 HMI High Feature firmware version V3.0 or higher SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Cooling time active Current limiting active Input control Input 1 Maximum pointer reset CPU/Master STOP Automatic mode Operating mode manual - bus Operating mode manual - local Factory settings restored Main power rotation right SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 183
Phase current I L1 min (rms) Phase current I L2 min (rms) Phase current I L3 min (rms) Phase current I L1 max (rms) Phase current I L2 max (rms) Phase current I L3 max (rms) SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 184
3RW52 soft starter in the past. Maximum pointers are based on measured values and represent the highest or smallest measured value that occurred in the past. 3RW52 soft starter from firmware version V2.0 SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
The display shows which keys must be actuated in sequence in order to perform the test. Test display The 3RW5 HMI High Feature runs a color program on the display. Navigate through the test operation with the OK key. SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Shows all active prewarnings and faults. You can acknowledge faults here. Additional information You will find further information on the diagnostics of the 3RW5 communication module in the Equipment Manual for the respective 3RW5 communication module. SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
The entire control circuit is tested, including the contact blocks and the error signaling output. If the 3RW52 soft starter responds correctly, no overload trip occurs. This can be reset immediately without a cooling-down period by pressing the TEST / RESET key again. SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 188
Display of test result pass fail "RN" Lights up green "ER" Lights up red "MT" Lights up yellow "STATE / OVERLOAD" Lights up yellow "RESET MODE" Lights up green "SOFT TORQUE" Lights up green SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 189
Lights up green yellow green Flickers Lights up Lights up green yellow green Flickers Lights up Lights up Lights up green yellow green green Flickers Lights up Lights up green yellow green SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 190
Self-test of the 3RW5 HMI High Feature You will find more information on the self-test of the 3RW5 HMI High Feature in Chapter Execute HMI diagnostics with the 3RW5 HMI High Feature (Page 185). SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
The device logbook is available in every module (3RW52 soft starter, 3RW5 HMI High Feature, 3RW5 communication module) and cannot be deleted. Saving logbooks The logbooks can be stored on a micro SD card (Page 166). SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
SD card. The service data can help Technical Support to handle the case in the event of a Support Request (Page 12). The service data contain the following data, for example: Parameters Logbooks Statistic data Maximum pointer I&M data SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 193
These service data can help Technical Support to handle the case in the event of a Support Request (Page 12). If necessary, read the micro SD card in at a PC and send the folder of service data as a ZIP file. SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 194
Messages and diagnostics 9.11 Save service data to micro SD card SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Touching live components will result in death or severe injury. Installation, commissioning, and maintenance only by qualified specialist personnel. Repair of the devices is only permissible by qualified personnel. Please contact the authorized Siemens service partner for this. SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
– With a fieldbus via a 3RW5 communication module with SIRIUS Soft Starter ES (TIA Portal) Premium / Professional or the configuration software of the controller (e.g. STEP 7 with corresponding HSP) (via a 3RW5 PROFINET or PROFIBUS communication module only) SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 197
You have performed a firmware update for the selected device. The selected device automatically restarts. Note Firmware update of the 3RW5 HMI High Feature: Please note that the display switches off for about 30 seconds when the firmware is activated. SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Please note that the display switches off for about 30 seconds when the firmware is activated. 3. Check the new firmware version in the "Overview" menu. Result You have performed a firmware update for the selected device using the micro SD card. SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
– The 3RW52 soft starter, the 3RW5 communication module, and the 3RW5 HMI High Feature are reset to the factory settings, as described above. Requirements The master control lies with the source of the command to restore the factory setting. SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 200
– With a fieldbus via a 3RW5 communication module with the configuration software of the control (only via a 3RW5 PROFINET or EtherNet/IP communication module). Only the communication parameters are reset here. Result The factory setting of the selected device or all devices is restored. SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
2. Confirm the menu item by pressing the OK key. Result The factory setting of the selected device or all devices is restored. Note the effects of the factory settings (Page 199). SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
3. Confirm the menu item by pressing the OK key. Result The factory setting of the selected device or all devices is restored. Note the effects of the factory settings (Page 199). SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
(e.g. flashing yellow if there is no main voltage (operating voltage)). 3. Release the MODE and RESET / TEST keys. Result The factory setting of the 3RW52 soft starter is restored. Note the effects of the factory settings (Page 199). SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Device parameters of the 3RW5 HMI High Feature Communication parameters Transmission options Device change with micro SD card on the 3RW5 HMI High Feature (Page 205) Device change with SIRIUS Soft Starter ES (TIA Portal) (Page 206) SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
3RW5 communication module) are overwritten by the data on the micro SD card. 3. Check the transferred data. Result You have transferred your saved data to your devices (3RW5 soft starter, 3RW5 HMI High Feature, 3RW5 communication module) with the "Device change" function. SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
2. Check the transferred data. Result You have transferred your saved data to your devices (3RW5 soft starter, 3RW5 HMI High Feature, 3RW5 communication module) with SIRIUS Soft Starter ES (TIA Portal). SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Technical data in Siemens Industry Online Support Technical data sheet You can also find the technical data of the product at Siemens Industry Online Support (https://support.industry.siemens.com/cs/ww/en/ps/16212/td). 1. Enter the full article number of the desired device in the "Product" field, and confirm with the Enter key.
Page 208
Technical specifications 11.1 Technical data in Siemens Industry Online Support SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Dimension drawings 12.1 CAx data You can find the CAx data in the Siemens Industry Online Support (https://support.industry.siemens.com/cs/ww/en/ps/16212/td). 1. Enter the full article number of the desired device in the "Product" field, and confirm with the Enter key. 2. Click the "CAx data link.
12.2 Drilling pattern for 3RW5 HMI Standard 12.2 Drilling pattern for 3RW5 HMI Standard The drilling pattern below supports you when installing a 3RW5 HMI Standard with push-in lugs on a level surface. SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
12.3 Drilling pattern for 3RW5 HMI High Feature 12.3 Drilling pattern for 3RW5 HMI High Feature The drilling pattern below supports you when installing a 3RW5 HMI High Feature with push-in lugs on a level surface. SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 212
Dimension drawings 12.3 Drilling pattern for 3RW5 HMI High Feature SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Circuit diagrams 13.1 CAx data You can find the CAx data in the Siemens Industry Online Support (https://support.industry.siemens.com/cs/ww/en/ps/16212/td). 1. Enter the full article number of the desired device in the "Product" field, and confirm with the Enter key. 2. Click the "CAx data link.
Connect the 3RW52 soft starter at its terminals to the motor feeder between the motor starter protector and the motor. This achieves type of coordination 1. Motor starter protector (e.g. 3RV2 or 3VA) 3RW52 soft starter Motor Protective conductor SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
The 3RW52 soft starter could otherwise indicate a "Missing load" fault in case of a start command and delayed connection of the contactor. gG full-range fuse for cable and line protection (e.g. 3NA3) Main or line contactor for galvanic isolation 3RW52 soft starter Motor Protective conductor SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
You must provide protection for all thyristors against short circuits by means of special semiconductor fuses (e.g. SITOR fuses from Siemens) to achieve type of coordination 2. A short circuit can occur, for instance, as a result of a defect in the motor windings or in the motor's power supply cable.
If the main voltage (operating voltage) is connected and the motor is connected to the 3RW52 soft starter, the 3RW52 soft starter automatically detects the motor connection type. Requirements Motor with windings that can be connected in a delta with line voltage predominating. SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 219
(e.g. SITOR 3NE3/4 or 3NC) gR full-range fuse for protection of semiconductors (e.g. SITOR 3NE1) 3RW52 soft starter Main or line contactor for galvanic isolation Motor Protective conductor SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 220
(e.g. SITOR 3NE3/4 or 3NC) gR full-range fuse for protection of semiconductors (e.g. SITOR 3NE1) 3RW52 soft starter Main or line contactor for galvanic isolation Motor Protective conductor SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
The example shows the 3RW52 soft starter in the inline circuit. Fuse Pushbutton: Start motor Pushbutton: Reset > 4 s Pushbutton: Stop motor Motor starter protector 3RW52 soft starter Motor Protective conductor SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Reset the start command (e.g. via the PLC or switch) before performing a reset. To do this, for example, link the group error output (terminals 95 and 96) into the control. SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 223
The example shows the 3RW52 soft starter in the inline circuit. Fuse Switch: Start/stop Pushbutton: Reset > 4 s Motor starter protector 3RW52 soft starter Motor Indicator light Indicator light Indicator light Protective conductor SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Reset the start command (e.g. via the PLC or switch) before performing a reset. To do this, for example, link the group error output (terminals 95 and 96) into the control. SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 225
The example shows the 3RW52 soft starter in the inline circuit. Fuse Switch: Reset > 4 s OFF Motor starter protector 3RW52 soft starter Motor Indicator light Indicator light Indicator light Protective conductor SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Reset the start command (e.g. via the PLC or switch) before performing a reset. To do this, for example, link the group error output (terminals 95 and 96) into the control. SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 227
Wiring of control circuit for control by PLC The example shows the 3RW52 soft starter in the inline circuit. Fuse Coupling relay control for reset > 4 s Motor starter protector 3RW52 soft starter Motor Protective conductor SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Reset the start command (e.g. via the PLC or switch) before performing a reset. To do this, for example, link the group error output (terminals 95 and 96) into the control. SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 229
The example shows the 3RW52 soft starter in the inline circuit. Fuse Switch: Start/stop Pushbutton: Reset > 4 s Motor starter protector 3RW52 soft starter Line contactor Motor Indicator light Indicator light Protective conductor SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Example circuits A.2 Control circuit connection A.2.6 Wiring for remote RESET Procedure Result You can reset a pending error message by operating the reset button for > 4 s. SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
The 3RW52 soft starter monitors the motor for excessive temperature. The motor is shut down if the maximum temperature limit is exceeded. The setting for RESET MODE (Page 105) determines how the motor is restarted. SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Disconnect the voltage at terminals AQ U+ / AQ- Disconnect the current at terminals AQ I+ / AQ- Result The actual average phase current of the motor is displayed in % at the evaluation unit via the analog output. SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Reset the start command (e.g. via the PLC or switch) before performing a reset. To do this, for example, link the group error output (terminals 95 and 96) into the control. SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 234
The example shows the 3RW52 soft starter in the inline circuit. Fuse Pushbutton: Motor ON - RIGHT Pushbutton: Motor ON - LEFT Pushbutton: Reset > 4 s Motor starter protector 3RW52 soft starter Contactor right Contactor left Indicator light Motor Protective conductor SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Reset the start command (e.g. via the PLC or switch) before performing a reset. To do this, for example, link the group error output (terminals 95 and 96) into the control. SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 236
Wiring The example shows the 3RW52 soft starter in the inline circuit. Fuse Switch: Start/stop Pushbutton: Reset > 4 s Motor starter protector 3RW52 soft starter Indicator light, fault Motor Protective conductor SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
"Missing load" fault message may be indicated on the 3RW52 soft starter. In this case, the 3RW52 soft starter must be reset according to the selected RESET MODE (Page 105). SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 238
3RW52 soft starter, together with a suitable safety relay (e.g.: 3SK1111), is required, as well as monitoring of the contactor's auxiliary contacts. Emergency stop 3RT20 contactor 3RW52 soft starter Motor 3SK1 safety relay SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 239
The example shows the 3RW52 soft starter in the inline circuit. Fuse Switch: Start / stop Pushbutton: Reset > 4 s Motor starter protector 3RW52 soft starter Contactor Indicator light Indicator light Motor Protective conductor SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 240
Example circuits A.3 Special applications Wiring of the 3SK1 safety relay SIL 1 with line contactor Fuse Line contactor Contactor Start button EMERGENCY STOP 3SK1111 safety relay SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 241
Example circuits A.3 Special applications Wiring of the 3SK1 safety relay SIL 1 without line contactor Fuse Contactor Start button EMERGENCY STOP 3SK1111 safety relay SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
"Missing load" fault message may be indicated on the 3RW52 soft starter. In this case, the 3RW52 soft starter must be reset according to the selected RESET MODE (Page 105). SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 243
2 redundant contactors and monitoring of the auxiliary contacts of both contactors. Two-channel monitoring of the EMERGENCY STOP is also required here. Emergency stop 3RT20 contactors 3RW52 soft starter Motor 3SK1 safety relay SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 244
A.3 Special applications Wiring of the 3RW52 soft starter Fuse Switch: Start / stop Pushbutton: Reset > 4 s Motor starter protector 3RW52 soft starter Contactor Contactor Indicator light Indicator light Motor Protective conductor SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 245
Example circuits A.3 Special applications Wiring of the 3SK1 safety relay SIL 3 with line contactor Fuse Fuse Line contactor Contactor Contactor Start button EMERGENCY STOP 3SK1111 safety relay SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 246
Example circuits A.3 Special applications Wiring of the 3SK1 safety relay SIL 3 without line contactor Fuse Fuse Contactor Contactor Start button EMERGENCY STOP 3SK1111 safety relay SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Reset the start command (e.g. via the PLC or switch) before performing a reset. To do this, for example, link the group error output (terminals 95 and 96) into the control. SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
OSS licenses by contacting the following address. SIEMENS may charge a handling fee of up to 5 Euro to fulfil the request. SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 250
Product or any OSS components contained in it if they are modified or used in any manner not specified by SIEMENS. The license conditions listed below may contain disclaimers that apply between you and the respective licensor.
Device master file This file is required to be able to configure a device as a DP standard slave in the HW Config of a Siemens or external system. GSDML Device master file This file is required to be able to configure a device as a DN device in the HW Config of a Siemens or external system.
Page 254
The soft starter can be configured with the STS (Simulation Tool for Soft Starters) software. The STS suggests suitable soft starters for the application based on the motor and load data and application requirements that you enter. SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
232 Device LEDs, 170, 171 Connecting the temperature sensor, 231 Disconnecting the control current form the screw Contactor for emergency start, 247 terminals, 89 Control by PLC, 226 Control by pushbutton, 221 SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 256
EMERGENCY STOP shutdown to SIL 3 or PL e with a I&M data, 160 3SK1 safety relay, 242 Inside-delta circuit, 218 ESD guidelines, 15 Interaction interfaces, 30 Example circuits Intrinsic device protection, 140 Inside-delta circuit, 218 SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 257
139 Structure of the article number, 44 Mounting, 53 Suggested settings, 101 Cover for control cable duct, 94 Switching with supply voltage Mounting on a level surface, 56 (control supply voltage), 224 SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...
Page 258
Current acquisition, 187 Motor overload protection, 187 Test with small load, 145 Thermistor motor protection with temperature sensor, 139 Third-party software information, 249 Warnings and remedial measures, 175 Wiring for remote RESET, 230 SIRIUS 3RW52 Soft Starter Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005...