Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
Fields of application........................15 Basic physical principles of a three-phase induction motor............15 3.2.1 Three-phase induction motor ..................... 15 Functional principle of the SIRIUS 3RW30 and 3RW40 soft starters........17 3.3.1 Method of operation of a two-phase controlled soft starter ............20 3.3.2 Starting current asymmetry .......................
Page 6
Application examples for heavy-duty starting (CLASS 20): 3RW40 only ........78 11.3 ON time and switching frequency ....................79 11.4 Reducing the rated data ......................80 11.5 Installation altitude and ambient temperature................80 SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
Page 7
Function of the FAILURE / OVERLOAD output ............... 112 12.10 RESET MODE and functions of the RESET / TEST button ............ 113 12.10.1 SIRIUS 3RW40 2. to 3RW40 4. soft starters ................113 SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
Page 8
13.2.24 Fused version (line protection only) ..................157 13.2.25 Fused version with SITOR 3NE1 fuses ................... 158 13.2.26 Fused version with SITOR 3NE3/4/8 fuses ................159 13.2.27 Motor protection tripping characteristics for 3RW40 (with symmetry) ........161 SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
Page 9
15.11.2 3RW40 2 to 3RW40 4 and Dahlander motor starting .............. 195 15.11.3 3RW40 5 to 3RW40 7 and Dahlander motor starting .............. 197 Accessories ............................199 16.1 Box terminal blocks for soft starters ..................199 16.2 Auxiliary conductor terminals....................199 SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
Page 10
Optional fan to increase the switching frequency (3RW40 2. to 3RW40 4.)......202 16.8 Spare parts for fans (3RW40 5., 3RW40 7.)................202 16.9 Operating instructions......................202 Appendix ..............................203 Configuration data ........................203 Table of parameters used......................205 Correction sheet ........................206 SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
The SIRIUS 3RW30 and 3RW40 soft starters are electronic motor control devices that facilitate optimal starting and stopping three-phase induction motors. The manual describes all of the functions of the SIRIUS 3RW30 and 3RW40 soft starters. Target group This manual is intended for any user involved in •...
Page 12
Your regional contact for low-voltage switchgear with communications capability will be happy to help you with any queries you have regarding the soft starters. A list of contacts and the latest version of the manual are available on the Internet at (www.siemens.com/softstarter): For all technical queries, please contact: Technical Assistance: Phone: +49 (0) 911-895-5900 (8°°...
These five safety rules must be applied in the above order prior to starting work on an electrical system. After completing the work, proceed in the reverse order. It is assumed that every electrician is familiar with these rules. SIRIUS 3RW30 / 3RW40 Manual 01/2010, 535 1995-02 DS01...
Page 14
5. These parts should be covered, or barriers erected around them, to avoid accidental contact during the work with adjacent parts that are still live. SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
The SIEMENS SIRIUS soft starter family comprises three different versions with different functionalities and prices. 3RW30 and 3RW40 Simple or standard applications are covered by the SIRIUS 3RW30 and 3RW40 soft starters and are described in this manual. 3RW44 The SIRIUS 3RW44 soft starter is used if higher functionality is specified, e.g. communication over PROFIBUS or the availability of measuring and monitoring values, as well as for ultra- heavy-duty starting.
From the point of view of the load machine, this means that the starting and acceleration forces exert a higher mechanical load on the machine and the product being conveyed compared to nominal operation. SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
Functional principle of the SIRIUS 3RW30 and 3RW40 soft starters The SIRIUS 3RW30 and 3RW40 soft starters have two antiparallel thyristors in two out of the three phases. One thyristor for the positive half-wave and one for the negative half-wave is provided in each phase (refer to Fig.
Page 18
Product description 3.3 Functional principle of the SIRIUS 3RW30 and 3RW40 soft starters Example SIEMENS 1LG4253AA motor (55 kW) Rated data at 400 V 55 kW 100 A Approx. 700 A direct starting 355 Nm ; e.g.: M = 9.55 x 55 kW x 1480 rpm Approx.
Page 19
The diagram below shows the method of operation of the SIRIUS 3RW30 and 3RW40 soft starters:...
3.3.1 Method of operation of a two-phase controlled soft starter A special method of operation is used for the SIRIUS 3RW30 and 3RW40 two-phase controlled soft starters based on SIEMENS' patented "polarity balancing" control principle. Two-phase control The SIRIUS 3RW30 and 3RW40 soft starters are two-phase controlled soft starters, in other words they are designed with two antiparallel thyristors in each of phases L1 and L3.
Product description 3.3 Functional principle of the SIRIUS 3RW30 and 3RW40 soft Polarity balancing "Polarity balancing" effectively eliminates these DC components during the ramp-up phase. It allows the motor to be started up with a constant speed, torque, and current rise.
Technical data [Page 121]. 3.3.3 Applications and use Applications and selection criteria The SIRIUS 3RW30 and 3RW40 soft starters represent a good alternative to direct or wye- delta starters. The most important advantages are: • Soft start •...
Page 23
Product description 3.3 Functional principle of the SIRIUS 3RW30 and 3RW40 soft Advantages Conveyor belts and transport systems: • Smooth starting • Smooth stopping Rotary pumps and piston pumps: • No pressure surges • Increased service life of the pipe system Agitators and mixers: •...
Technical data [Page 121]. For further information on individual products, refer to System manual (http:// support.automation.siemens.com/WW/ llisapi.dll?aktprim=0&lang=en&referer=%2fWW%2f&func=cslib.csinfo&siteid=csius&caller=vi ew&extranet=standard&viewreg=WW&nodeid0=20025979&objaction=csopen) "Innovations in the SIRIUS modular system", Order No. 3ZX1012-0RA01-1AB1. SIRIUS 3RW30 / 3RW40 Manual 01/2010, 535 1995-02 DS01...
Functions Start modes You can choose between different startup functions reflecting the wide range of applications and functionality of the SIRIUS 3RW30 and 3RW40 soft starters. The motor start can be optimally adapted to each particular application. 5.1.1 Voltage ramp The SIRIUS 3RW30 and 3RW40 soft starters achieve soft starting by means of a voltage ramp.
Page 28
When using the 3RW40: The 3RW40 has an integrated ramp-up detection function that prevents this operating state from occurring. The maximum ramp time for the SIRIUS 3RW30 soft starter is 20 seconds An appropriately dimensioned SIRIUS 3RW40 or 3RW44 soft starter should be chosen for startup processes with a motor ramp-up time >...
If the current limiting value is set to 100 A, the currents might be approx. 80 A in L1, 120 A in L2, and 100 A in L3 (refer to chapter Starting current asymmetry [Page 21]). SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
If you select "soft stop" (3RW40 only) as the stop mode, the feeder (soft starter, cables, feeder protective devices, and motor) may need to be dimensioned for higher values because the current exceeds the rated motor current during the stop process. SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
It has the effect of producing noise and mechanical impacts on the pipelines as well as on any flaps and valves installed there. SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
This indicates whether the motor is overloaded or functioning in the normal operating range. The winding temperature can either be calculated with the help of the integrated, electronic motor overload function or measured with a connected motor thermistor. SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
Page 33
Wire the fault output (95 96) to an upstream switching device in such a way that if a fault occurs, this device disconnects the feeder (refer to Fig. "3RW40 wiring fault with 3RV"). Figure 5-5 3RW40 wiring fault SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
Page 34
Technical data [Page 121]). Recovery time (motor overload protection) A recovery time of 60 seconds, during which the motor cools down and cannot be restarted, starts if the thermal motor model is tripped. SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
If the fixed, internally set trip value is exceeded, the soft starter is automatically disconnected. Recovery time (intrinsic device protection) If the intrinsic device protection is tripped, the soft starter cannot be restarted until a recovery time of at least 30 seconds has elapsed. SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
Green = REMOTE Note On the SIRIUS 3RW40 2. soft starter, the RESET MODE button is located underneath the label (refer to chapter Operator controls, displays, and connections on the 3RW40 [Page 70]) SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
Page 37
Acknowledging faults For information about whether or not faults can be acknowledged as well as the corresponding LED and output contact states, refer to chapter Diagnostics and fault signals [Page 44]. SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
You can reset a fault by pressing the RESET / TEST button. 5.4.2.3 Remote RESET Remote RESET (AUTO LED = green) You can initiate a remote RESET by controlling the optional module for RESET (3RU1900- 2A). SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
3RW40 7 5.4.3.2 Reparameterizing the ON / RUN output contact For information about reparameterizing the output with the RESET / TEST button, refer to chapter Parameterizing the 3RW40 outputs [Page 110] . SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
If you select direct control by a PLC, the "M" of the PLC's reference potential must be connected to terminal 2 (-). For recommended circuits, e.g. control by means of pushbuttons, contactor contacts, or a PLC, refer to chapter Typical circuit diagrams [Page 167]. SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
The output can be used, for instance, to control a line contactor connected upstream or to implement latching if you selected pushbutton control. For recommended circuits, refer to chapter Typical circuit diagrams [Page 167]. R on R on 13/14 R on SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
The integral bypass contacts simultaneously close and the thyristors are bridged. The integral bypass contacts and output 23 / 24 open again as soon as the start input IN is removed. SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
For recommended circuits, refer to chapter Typical circuit diagrams [Page 167]. For a state diagram of the contacts in the various fault and operating states, refer to chapter Diagnostics and fault signals [Page 44]. SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
2) The fault can be acknowledged by removing the start command at the start input. 3) Switch off the control voltage, then switch it on again. If the fault is still present, contact your SIEMENS partner or Technical Assistance. For notes on troubleshooting, refer to the table below.
Page 45
Cause 3: Motor phase T1 / T2 / T3 is not Connect the motor properly (e.g. jumpers connected. in the motor terminal box, repair switch closed etc.) Device fault Soft starter defective. Contact your SIEMENS partner or Technical Assistance. SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
Functions 5.7 Diagnostics and fault signals 5.7.2 3RW40: LEDs and troubleshooting SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
Page 47
Rectify the causes and possibly retrofit • Motor ramp-up time too long, the optional fan (3RW40 2. to 3RW40 4.). • Ambient temperature in switching device's environment too high, • Minimum installation clearances not complied with. SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
Page 48
• Minimum installation clearances not soft starter's environment is too high complied with. (derating above 40 °C, refer to chapter Technical data [Page 121]), comply with the minimum clearances. SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
Page 49
Cause 3: Motor phase T1 / T2 / T3 is not Connect the motor properly (e.g. jumpers connected. in the motor terminal box, repair switch closed etc.) Device fault Soft starter defective. Contact your SIEMENS partner or Technical Assistance. SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
The feeder assembly should be as small as possible so as not to exceed the control cabinet's space capacity. The SIRIUS 3RW30 soft starter offers the following advantages: • The roller conveyor is rapidly accelerated to the nominal speed without torque surges thanks to the optimum setting of the voltage ramp during startup.
Motor protection is ensured by the motor overload relay with settable tripping times integrated in the soft starter. • The adjustable voltage ramp ensures that the hydraulic pump is started and stopped without torque surges. SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
An optional fan can be ordered for the 3RW40 24 to 3RW40 47 sizes; this fan is integrated in the device for 3RW40 55 to 3RW40 76. The 3RW30 cannot be equipped with a fan. SIRIUS 3RW30 / 3RW40 Manual 01/2010, 535 1995-02 DS01...
0.59 2.36 1.56 3RW40 3./3RW40 4. 1.18 2.36 1.56 3RW40 5./3RW40 7. NOTICE Allow sufficient clearances for the cooling air to circulate freely. The device is ventilated from bottom to top. SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
The term "side-by-side assembly" is used if the lateral clearance a described in chapter Mounting dimensions, clearances, and assembly type [Page 54] are not complied with, e.g. if several switching devices are assembled side by side. SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
Installation requirements Degree of protection IP00 The SIRIUS 3RW30 / 3RW40 soft starters conform to the IP00 degree of protection. The devices must be installed in control cabinets with the IP54 degree of protection (pollution degree 2), taking account of the ambient conditions.
SIRIUS 3RW40 soft starter. The motor overload protection for the SIRIUS 3RW30 soft starter can be implemented with a motor circuit breaker, for instance, or using a motor overload relay in conjunction with a contactor (for the fuse and motor starter protector assignment, refer to Technical data [Page 121]).
5. These parts should be covered, or barriers erected around them, to avoid accidental contact during the work with adjacent parts that are still live. SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
8.3 General feeder assembly (type of coordination 1) General feeder assembly (type of coordination 1) The SIRIUS 3RW30 or 3RW40 soft starter is connected into the motor feeder between the motor starter protector and the motor. 3/N/PE~ 50 Hz 400 V...
If a main or line contactor is used, it should not be connected between the soft starter and the motor. The soft starter could otherwise indicate a "Missing load voltage" fault in case of a start command and delayed connection of the contactor. SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
1 is achieved. In order to achieve type of coordination 2, all thyristors must be additionally protected against short-circuits by means of special semiconductor fuses (e.g. SIEMENS SITOR). A short-circuit can occur, for instance, as a result of a defect in the motor windings or in the motor's power supply cable.
If an isolating or main contactor is used together with the electronic soft starter, the capacitors must be disconnected from the soft starter when the contactor is open. SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
The voltage drop due to the length of the cable to the motor may need to be considered when dimensioning the cable. Cable lengths up to 500 m are permitted for SIRIUS 3RW44 soft starters (refer to the 3RW44 System Manual (http://support.automation.siemens.com/WW/ llisapi.dll?query=3RW44&func=cslib.cssearch&content=skm%2Fmain.asp&lang=de&siteid=c sius&objaction=cssearch&searchinprim=0&nodeid0=20025979)). SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
Spring-loaded technology 9.1.2 Main circuit connection SIRIUS 3RW30 and 3RW40 soft starters up to the 55 kW / 75 hp size at 400 V / 480 V are designed with removable terminals at the main circuit connections. SIRIUS 3RW30 / 3RW40...
Operator controls, displays, and connections on the 3RW30 Operating voltage (three-phase mains voltage) Control supply voltage IN start input ON output DEVICE status LED STATE / BYPASSED / FAILURE status LED Ramp-up time Starting voltage Motor terminals SIRIUS 3RW30 / 3RW40 Manual 01/2010, 535 1995-02 DS01...
Thermistor input (can be optionally ordered with 24 V AC/DC control voltage for 3RW40 2. to 3RW40 4. devices) Fault output Motor terminals RESET MODE button (behind the label on the 3RW40 2., refer to the diagram below) SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
Page 71
Operation 10.2 Operator controls, displays, and connections on the 3RW40 3RW40 2... RESET MODE Figure 10-1 Button for setting RESET MODE behind the label SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
Page 72
Operation 10.2 Operator controls, displays, and connections on the 3RW40 SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
11.1 Configuration in general The SIRIUS 3RW30 and 3RW40 electronic soft starters are designed for normal starting. A larger size may need to be selected for longer ramp-up times or a higher starting frequency. An appropriately dimensioned SIRIUS 3RW40 or 3RW44 soft starter should be chosen for startup processes with motor ramp-up times >...
1) Small fan: Mass inertia (centrifugal mass) of fan < 10 x mass inertia of motor Heavy-duty starting (CLASS 20) 3RW30 3RW40 3RW44 applications Agitator Extruder Turning machine Milling machine + Recommended soft starter x Possible soft starter SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
Page 75
+ Recommended soft starter Note SIRIUS 3RW44 soft starter For more information about the SIRIUS soft starter, refer to the 3RW44 System Manual. You can download (http://support.automation.siemens.com/WW/ llisapi.dll?func=cslib.csinfo&lang=de&objID=20356385&subtype=133300) the manual free of charge. SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
When using the 3RW30: Make sure the selected ramp time is longer than the actual motor ramp-up time. If not, the SIRIUS 3RW30 may be damaged because the internal bypass contacts close when the set ramp time elapses. If the motor has not finished starting up, an AC3 current that could damage the bypass contact system will flow.
3RW40: Maximum ramp-up time 10 s, 300 % current limiting, 5 starts / hour ON time 30 % Standalone assembly Installation altitude Max. 1000 m / 3280 ft Ambient temperature kW 40 °C / 104 °F SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
If other conditions and constraints apply, either refer to chapter Technical data [Page 121] or check your requirements and selection with the Win-Soft Starter software or with Technical Assistance (chapter Important notes [Page 11]) SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
11.3 ON time and switching frequency Based on the rated motor current and the startup class, the SIRIUS 3RW30 and 3RW40 soft starters are dimensioned for a maximum permissible switching frequency in combination with a relative ON time (refer to chapter Technical data [Page 121]). If these values are exceeded, a larger soft starter may have to be selected.
Configuration 11.4 Reducing the rated data 11.4 Reducing the rated data You can reduce the rated data of the SIRIUS 3RW30 and 3RW40 soft starters if • The installation altitude is higher than 1000 m. • The ambient temperature in the switching device's environment exceeds 40 °C.
Table of permissible assembly combinations with switching frequency factors The factors indicated in the table refer to the switching frequency (starts / hour) as specified in chapter Technical data [Page 121]. SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
Page 82
Configuration 11.6 Calculating the permissible switching frequency SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
Page 83
Configuration 11.6 Calculating the permissible switching frequency SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
(e.g. a pump motor with CLASS 10 starting). The soft starter must be connected to a 3RV2021 motor starter protector by means of cables. (Clearance between 3RV and 3RW >= 40 mm) SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
Page 85
The pump could be started five times an hour providing the above assembly conditions are complied with (side-by-side assembly, vertical mounting). A switching frequency of up to 80 starts per hour can be achieved by equipping the 3RW4026 with the optional 3RW4928- 8VB00 fan. SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
11.7.2 Win-Soft Starter selection and simulation software The Win-Soft Starter software can be used to simulate and select all SIEMENS soft starters, taking into account various parameters such as the supply system conditions, motor data, load data, high switching frequencies etc.
11.7 Configuration aids 11.7.4 SIRIUS soft starter training course (SD-SIRIUSO) SIEMENS offers a two-day training course on SIRIUS electronic soft starters to keep both customers and our own employees up to date with the latest information about configuring, commissioning, and maintenance.
Pe = 45 kW / 50 hp Size S3 Ie = 106 A / 398 A Pe = 55 kW / 75 hp For more information, refer to chapter Technical data [Page 121]. SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
Pe = 200 kW / 250 hp Ie = 432 A / 385 A Pe = 250 kW / 300 hp For more information, refer to chapter Technical data [Page 121]. SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
Page 90
Configuration 11.9 Order number system for the 3RW40 SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
For the purpose of the safety information in these Operating Instructions, a "qualified person" is someone who is authorized to energize, ground, and tag equipment, systems, and circuits in accordance with established safety procedures. SIRIUS 3RW30 / 3RW40 Manual 01/2010, 535 1995-02 DS01...
3. Start up the motor and if necessary optimize the parameters (refer to the quick commissioning table). 4. Document the parameter settings if required (refer to chapter Table of parameters used [Page 205]). SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
Commissioning 12.2 Commissioning the 3RW30 12.2.2 Quick commissioning of the 3RW30 and optimization of the parameters SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
12.2.3 Setting the soft start function Voltage ramp The SIRIUS 3RW30 achieves soft starting by means of a voltage ramp. The motor terminal voltage is increased from a parameterizable starting voltage to the mains voltage within a definable ramp time.
The SIRIUS 3RW30 soft starter can be damaged in this application (set ramp time shorter than the actual motor ramp-up time). A maximum ramp-up time of 20 s is possible for the 3RW30.
Make sure the selected ramp time is longer than the actual motor ramp-up time. If not, the SIRIUS 3RW30 may be damaged because the internal bypass contacts close when the set ramp time elapses. If the motor has not finished starting up, an AC3 current that could damage the bypass contact system will flow.
2) The fault can be acknowledged by removing the start command at the start input. 3) Switch off the control voltage, then switch it on again. If the fault is still present, contact your SIEMENS partner or Technical Assistance. For notes on troubleshooting, refer to the table below.
Device fault Soft starter defective. Contact your SIEMENS partner or Technical Assistance. 12.4 Commissioning the 3RW40 Commissioning, description of the start, stop, motor protection, and output parameters SIRIUS 3RW30 / 3RW40...
4. Define the RESET mode if a failure occurs. 5. Start up the motor and if necessary optimize the parameters (refer to the quick commissioning table). 6. Document the parameter settings if required. SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
Commissioning 12.4 Commissioning the 3RW40 12.4.2 Quick commissioning of the 3RW40 and optimization of the parameters SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
The SIRIUS 3RW40 achieves soft starting by means of a voltage ramp. The motor terminal voltage is increased from a parameterizable starting voltage to the mains voltage within a definable ramp time. SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
(for further information about the maximum ramp-up times and switching frequencies, refer to the Technical data chapter > 3RW30 13, 14, 16, 17, 18-.BB.. power electronics [Page 124]) ff. and 3RW40 24, 26, 27, 28 power electronics [Page 149] ff.). SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
Setting the motor current potentiometer The rated operational current of the motor must be set with the I potentiometer according to the mains voltage and the motor connection (wye-delta). The electronic motor overload SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
100 % of the mains voltage. The thyristors of the soft starter are bridged by the bypass contacts integrated in the device and the successful startup is indicated by means of the BYPASS output and the STATE / BYPASSED LED. SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
This indicates whether the motor is overloaded or functioning in the normal operating range. The winding temperature can either be calculated with the help of the integrated, electronic motor overload function or measured with a connected motor thermistor. SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
Motor current settings [Page 107]); if not, a fault will be indicated by the OVERLOAD LED (red flashing ) and it will not be possible to start the SIRIUS 3RW soft starter. SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
The SIRIUS 3RW40 soft starter is tripped by the fault signal at the OVERLOAD LED, the FAILURE / OVERLOAD contact 95-98 closes, and the motor that is connected and running is switched off. SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
If the RUN function is set, you can control a line contactor during the startup process, operation, or the set soft stop (refer to chapter Control with an optional main / line contactor [Page 177]) SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
DEVICE STATE/BYPASSED FAILURE RESET MODE RESET /TEST RESET MODE CLASS 100% Figure 12-2 Overview of buttons / LEDs on the 3RW40 2 to 3RW40 4 and 3RW40 5 to 3RW40 7 SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
Page 111
Press the RESET / TEST MODE button (1) for longer than 1 s until the DEVICE LED (3) lights up (green). The LEDs indicate the following states again if the output was successfully parameterized: SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
For information about whether or not faults can be acknowledged, as well as the recovery time and the corresponding LED and output contact states, refer to chapter Diagnostics and fault signals [Page 44]. SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
By pressing the RESET MODE button, you define the reset procedure in case of a fault. This is indicated by the RESET MODE LED. 12.10.1.2 Manual RESET RESET / TEST button (RESET MODE LED off) You can reset a fault by pressing the RESET / TEST button. SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
Page 114
For safety reasons, you are advised to integrate the group fault output on the 3RW40 (terminals 95 and 96), or the signaling contact of the motor or miniature circuit breaker on all devices, in the controller. SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
By pressing the RESET MODE button, you define the reset procedure in case of a fault. This is indicated by the AUTO LED. 12.10.2.2 Manual RESET RESET / TEST button (AUTO LED off) You can reset a fault by pressing the RESET / TEST button. SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
Page 116
For safety reasons, you are advised to integrate the group fault output on the 3RW40 (terminals 95 and 96), or the signaling contact of the motor or miniature circuit breaker on all devices, in the controller. SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
Commissioning 12.11 3RW40: LEDs and troubleshooting 12.11 3RW40: LEDs and troubleshooting SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
Page 118
Rectify the causes and possibly retrofit • Motor ramp-up time too long, the optional fan (3RW40 2. to 3RW40 4.). • Ambient temperature in switching device's environment too high, • Minimum installation clearances not complied with. SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
Page 119
• Minimum installation clearances not soft starter's environment is too high complied with. (derating above 40 °C, refer to chapter Technical data [Page 121]), comply with the minimum clearances. SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
Page 120
Cause 3: Motor phase T1 / T2 / T3 is not Connect the motor properly (e.g. jumpers connected. in the motor terminal box, repair switch closed etc.) Device fault Soft starter defective. Contact your SIEMENS partner or Technical Assistance. SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
13.1.1 Overview SIRIUS 3RW30 soft starters reduce the motor voltage through variable phase angle control and increase it from a selectable starting voltage up to the mains voltage within the ramp time. They limit the starting current and torque, so that the shocks that occur during direct starts or wye-delta starting are avoided.
We recommend using the "Win-Soft Starter" selection and simulation software. For information about the rated currents for ambient temperatures > 40 °C, refer to chapter 3RW30..-.BB.. power electronics [Page 124]. SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
Technical data 13.1 3RW30 13.1.3 3RW30..-.BB.. control electronics 13.1.4 3RW30..-.BB.. control times and parameters SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
Required for 3RW303. and 3RW304. (see table) 1) Degree of noise suppression B cannot be obtained through the use of filters as the strength of the electromagnetic field is not attenuated by the filter. SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
The type of coordination only refers to soft starters in conjunction with the stipulated protective device (motor starter protector / fuse), not to additional components in the feeder. SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
Technical data 13.1 3RW30 13.1.14 Fuseless version The rated motor current must be The types of coordination are described in considered when selecting the devices. chapter Types of coordination [Page 128]. SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
Type of coordination 1 only refers to soft 5SE2 201-6 (NEOZED). starters in conjunction with the stipulated protective device (motor starter protector / fuse), not to any additional components in the feeder. SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
Type of coordination 2 only refers to soft Alternatively: 3NA3 803 (NH00), 5SB2 21 starters in conjunction with the stipulated (DIAZED), 5SE2 206 (NEOZED) protective device (motor starter protector / fuse), not to additional components in the feeder. SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
Technical data 13.1 3RW30 13.1.17 Fused version with SITOR 3NE3/4/8 fuses Assembly as for type of coordination 2, with additional SITOR fuses (F3) for thyristor protection only. SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
Page 133
Types of coordination [Page 128]. Type of coordination 2 only refers to soft starters in conjunction with the stipulated protective device (motor starter protector / fuse), not to additional components in the feeder. SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
"Increased safety" type of protection EEx e according to ATEX Directive 94/9/EC The SIRIUS 3RW40 soft starter sizes S0 to S12 are suitable for starting explosion-proof motors with the "increased safety" type of protection EEx e. SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
Technical data 13.2 3RW40 13.2.2 Selection and ordering data for standard applications and normal starting (CLASS 10) SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
Page 136
We recommend using the "Win-Soft Starter" selection and simulation software. For information about the rated currents for ambient temperatures > 40 °C, refer to chapter 3RW40 2. to 7. power electronics [Page 148]. SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
Technical data 13.2 3RW40 13.2.3 Selection and ordering data for standard applications and normal starting (CLASS 10) (with thermistor motor protection evaluation) SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
Page 138
We recommend using the "Win-Soft Starter" selection and simulation software. For information about the rated currents for ambient temperatures > 40 °C, refer to chapter 3RW40 2. to 7. power electronics [Page 148]. SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
Technical data 13.2 3RW40 13.2.4 Selection and ordering data for standard applications and normal starting (CLASS 10) SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
Page 140
We recommend using the "Win-Soft Starter" selection and simulation software. For information about the rated currents for ambient temperatures > 40 °C, refer to chapter 3RW40 2. to 7. power electronics [Page 148]. SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
Technical data 13.2 3RW40 13.2.5 Selection and ordering data for standard applications and heavy-duty starting (CLASS 20) SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
Page 142
We recommend using the "Win-Soft Starter" selection and simulation software. For information about the rated currents for ambient temperatures > 40 °C, refer to chapter 3RW40 24, 26, 27, 28 power electronics [Page 149]. SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
Technical data 13.2 3RW40 13.2.6 Selection and ordering data for standard applications and heavy-duty starting (CLASS 20) SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
Page 144
We recommend using the "Win-Soft Starter" selection and simulation software. For information about the rated currents for ambient temperatures > 40 °C, refer to chapter 3RW40 55, 56, 73, 74, 75, 76 power electronics [Page 151]. SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
The type of coordination only refers to soft starters in conjunction with the stipulated protective device (motor starter protector / fuse), not to additional components in the feeder. SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
Types of coordination [Page 155]. 3RV13 and 3RV23 motor starter protectors are used for starter combinations (without motor protection). In this case, motor protection is provided by the 3RW40 soft starter. SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
The types of coordination are described in chapter Types of coordination [Page 155]. Type of coordination 1 only refers to soft starters in conjunction with the stipulated protective device (motor starter protector / fuse), not to additional components in the feeder. SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
The types of coordination are described in chapter Types of coordination [Page 155]. Type of coordination 2 only refers to soft starters in conjunction with the stipulated protective device (motor starter protector / fuse), not to additional components in the feeder. SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
Technical data 13.2 3RW40 13.2.26 Fused version with SITOR 3NE3/4/8 fuses Assembly as for type of coordination 2, with additional SITOR fuses (F3) for thyristor protection only. SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
Page 160
The types of coordination are described in chapter Types of coordination [Page 155]. Type of coordination 2 only refers to soft starters in conjunction with the stipulated protective device (motor starter protector / fuse), not to additional components in the feeder. SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
13.3 Win-Soft Starter selection and simulation software 13.3 Win-Soft Starter selection and simulation software This software can be used to simulate and select all SIEMENS soft starters, taking into account various parameters such as the supply system conditions, motor data, load data, specific application requirements, etc.
3RW40 2 to 3RW40 4. Note If a thermistor is connected (PTC type A or Klixon), you must remove the copper jumper between terminals T11/21 and T22. Figure 15-1 Optional thermistor motor protection evaluation SIRIUS 3RW30 / 3RW40 Manual 01/2010, 535 1995-02 DS01...
If you do not want the motor to start automatically, you must integrate suitable additional components, e.g. phase failure or load monitoring devices, into the control and main circuits. SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
1 or 2. For the assignment of fuses and switching devices, refer to chapter Technical data [Page 121] For the optional thermistor motor protection evaluation, refer to Typical circuit for the optional thermistor motor protection evaluation [Page 167]. SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
(3) Alternatively, the motor feeder can be assembled as a fuseless or fused version with type of coordination 1 or 2. For the assignment of fuses and switching devices, refer to chapter Technical data [Page 121] SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
Wiring of the 3RW40 5 to 3RW40 7 control circuit (1) For the permissible values for the main and control voltage (dependent on the MLFB), refer to chapter Technical data [Page 121] . SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
Wiring of the 3RW30 control and main circuits (1) For the permissible values for the main and control voltage (dependent on the MLFB), refer to chapter Technical data [Page 121] . SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
Technical data [Page 121] 15.4.2 Control of the 3RW40 in automatic mode Figure 15-9 Wiring of the 3RW40 2 to 3RW40 4 control circuit and the 3RW40 2 to 3RW40 7 main circuit SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
Page 174
Owing to the intrinsic protection (3RW), an idle time of at least five minutes must be allowed prior to restarting if the device is switched on and off by means of the control voltage under field conditions. > 5 min SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
(3) Alternatively, the motor feeder can be assembled as a fuseless or fused version with type of coordination 1 or 2. For the assignment of fuses and switching devices, refer to chapter Technical data [Page 121] SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
Figure 15-13 Wiring of the 3RW40 5 to 3RW40 7 control circuit (1) For the permissible values for the main and control voltage (dependent on the MLFB), refer to chapter Technical data [Page 121] . SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
Figure 15-14 Wiring of the 3RW30 control and main circuits (1) For the permissible values for the main and control voltage (dependent on the MLFB), refer to chapter Technical data [Page 121] . SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
Technical data [Page 121] 15.6.2 Control of the 3RW40 with a main contactor Figure 15-15 Wiring of the 3RW40 2 to 3RW40 4 control circuit and the 3RW40 2 to 3RW40 7 main circuit SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
Page 179
1 or 2. For the assignment of fuses and switching devices, refer to chapter Technical data [Page 121] For the optional thermistor motor protection evaluation, refer to Typical circuit for the optional thermistor motor protection evaluation [Page 167]. SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
(3) Alternatively, the motor feeder can be assembled as a fuseless or fused version with type of coordination 1 or 2. For the assignment of fuses and switching devices, refer to chapter Technical data [Page 121] SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
Typical circuit diagrams 15.7 Reversing circuit 15.7.2 3RW40 reversing circuit Figure 15-18 Wiring of the 3RW40 2 to 3RW40 5 control circuit and the 3RW40 2 to 3RW40 7 main circuit SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
Page 182
For the optional thermistor motor protection evaluation, refer to Typical circuit for the optional thermistor motor protection evaluation [Page 167]. NOTICE No soft stop possible. Set the ramp-down time to 0 s with the potentiometer. SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
(3) Alternatively, the motor feeder can be assembled as a fuseless or fused version with type of coordination 1 or 2. For the assignment of fuses and switching devices, refer to chapter Technical data [Page 121] SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
For the optional thermistor motor protection evaluation, refer to Typical circuit for the optional thermistor motor protection evaluation [Page 167]. NOTICE No soft stop possible. Set the ramp-down time to 0 s with the potentiometer. SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
For the optional thermistor motor protection evaluation, refer to Typical circuit for the optional thermistor motor protection evaluation [Page 167]. NOTICE No soft stop possible. Set the ramp-down time to 0 s with the potentiometer. SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
3RW30 emergency stop and 3TK2823 safety relay Figure 15-23 Wiring of the emergency stop control circuit and the 3TK28 safety relay Figure 15-24 Wiring of the 3RW30 control and main circuits SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
1 or 2. For the assignment of fuses and switching devices, refer to chapter Technical data [Page 121] 15.9.2 3RW40 2 to 3RW40 4 emergency stop and 3TK2823 safety relay Figure 15-25 Wiring of the emergency stop control circuit and the 3TK28 safety relay SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
Page 188
"Missing load voltage, phase failure / missing load" fault may be indicated on the soft starter. In this case, the soft starter must be reset according to the selected RESET MODE. SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
Wiring of the 3RW40 5 to 3RW40 7 control circuit and the 3RW40 2 to 3RW40 7 main circuit (1) For the permissible values for the main and control voltage (dependent on the MLFB), refer to chapter Technical data [Page 121] . SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
Page 190
"Missing load voltage, phase failure / missing load" fault may be indicated on the soft starter. In this case, the soft starter must be reset according to the selected RESET MODE. SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
(3) Alternatively, the motor feeder can be assembled as a fuseless or fused version with type of coordination 1 or 2. For the assignment of fuses and switching devices, refer to chapter Technical data [Page 121] SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
Wiring of the 3RW40 2 to 3RW40 4 control circuit and the 3RW40 2 to 3RW40 7 main circuit Figure 15-31 Wiring of the 3RW40 5 to 3RW40 7 control circuit SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
Page 193
1 or 2. For the assignment of fuses and switching devices, refer to chapter Technical data [Page 121] For the optional thermistor motor protection evaluation, refer to Typical circuit for the optional thermistor motor protection evaluation [Page 167]. SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
If you do not want the motor to start automatically, you must integrate suitable additional components, e.g. phase failure or load monitoring devices, into the control and main circuits. SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
Wiring of the 3RW40 2 to 3RW40 4 control circuit and the 3RW40 2 to 3RW40 7 main circuit (1) For the permissible values for the main and control voltage (dependent on the MLFB), refer to chapter Technical data [Page 121] . SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
Page 196
For the optional thermistor motor protection evaluation, refer to Typical circuit for the optional thermistor motor protection evaluation [Page 167]. NOTICE No soft stop possible. Set the ramp-down time to 0 s with the potentiometer. SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
Typical circuit diagrams 15.11 Dahlander / multispeed motor 15.11.3 3RW40 5 to 3RW40 7 and Dahlander motor starting Figure 15-34 Wiring of the 3RW40 5 to 3RW40 7 control circuit SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
Page 198
1 or 2. For the assignment of fuses and switching devices, refer to chapter Technical data [Page 121] NOTICE No soft stop possible. Set the ramp-down time to 0 s with the potentiometer. SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
For complying with the phase clearances and as touch protection if box terminal is removed (2 units required per contactor) 3RW30 4. 3RT19 46-4EA1 3RW40 4. 3RW40 5. 3RT19 56-4EA1 3RW40 7. 3RT19 66-4EA1 SIRIUS 3RW30 / 3RW40 Manual 01/2010, 535 1995-02 DS01...
(The speed increments of the value pairs do not have to be equal) "n " Speed / current characteristic curve (The speed increments of the value pairs do not have to be equal) "n " SIRIUS 3RW30 / 3RW40 Manual 01/2010, 535 1995-02 DS01...
Appendix A.2 Table of parameters used Table of parameters used You can document your parameter settings in the table below. SIRIUS 3RW30 / 3RW40 Manual, 01/2010, 535 1995-02 DS01...
Address Phone Fax: 0 96 21 / 80-33 37 System Manual for SIRIUS 3RW30 / 3RW40 soft starters Have you noticed any errors while reading this manual? If so, please use this form to tell us about them. We welcome comments and suggestions for improvement.