Description
1.5 Operating modes and master control function
"Automatic" mode
For the "Automatic" mode you require a 3RW5 communication module and a higher-level
control (e.g. PLC). The control source is connected to the 3RW50 soft starter via the
3RW5 communication module.
In the "Automatic" mode the master control function rests with a higher-level control:
● PROFINET, PROFIBUS, EtherNet/IP: Programmable logic controller (PLC)
● Modbus TCP: Modbus Client (e.g. PLC)
● Modbus RTU: Modbus Master (e.g. PLC)
Operating mode "manual - bus"
For the "Manual-bus" mode you require a 3RW5 PROFINET or PROFIBUS communication
module and a PC with SIRIUS Soft Starter ES (TIA Portal) Premium. The control source is
connected to the 3RW50 soft starter via the 3RW5 communication module.
In the operating mode "manual - bus" the master control function rests with the
SIRIUS Soft Starter ES (TIA Portal) Premium software.
Operating mode "manual - local"
In the operating mode "manual - local" the master control function rests with a control source
directly on the 3RW50 soft starter:
● Input IN
● 3RW5 HMI (accessories)
● SIRIUS Soft Starter ES (TIA Portal) via local interface on the 3RW5 HMI High Feature
(accessory)
Priorities of the operating modes
Mode
Automatic
Manual - bus
(depending on the 3RW5
communication module)
Manual - local
Explanation in text below
1)
Lowest priority without 3RW5 communication module
2)
16
Control source
Higher-level control (e.g. PLC)
-
Connection abort
PC controlled
SIRIUS Soft Starter ES (TIA Portal) Premium
Input controlled
Input IN
3RW5 HMI controls
3RW5 HMI
PC controlled
SIRIUS Soft Starter ES (TIA Portal)
1)
SIRIUS 3RW50 soft starter
Manual, 09/2019, A5E35628455002A/RS-AA/001
Priority
Lowest
2)
Highest