Parameter assignment
5.7 Parameterizing output 13 / 14 (output signal ON or RUN)
4. Switch the mode by pressing the MODE key briefly. The SOFT TORQUE LED switches
between flickering green and flashing green.
You can switch between the modes at the output as often as you want.
Note
If you do not press a key in the programming mode for longer than 10 s, the
3RW50 soft starter automatically terminates the programming mode.
5. Terminate programming mode by pressing the RESET / TEST key for longer than 1 s
until the STATE / OVERLOAD LED no longer shines red.
Tip
Alternatively, output 13 / 14 may also be set in the "Parameters > Soft Starter > ON / RUN
relay output" menu of the 3RW5 HMI High Feature (accessories).
100
SIRIUS 3RW50 soft starter
Manual, 09/2019, A5E35628455002A/RS-AA/001