Connecting
4.1 Connections
①
②
③
④
⑤
⑥
⑦
⑧
Note
Parameterizing output 13 / 14
You will find more information on parameterization in Chapter Parameterizing output 13 / 14
(output signal ON or RUN) (Page 99).
Note
Parameterizing the analog output
You can parameterize the output of the analog output with the 3RW5 HMI High Feature
(Page 111).
70
Main circuit connection network 1 / L1, 3 / L2, 5 / L3
A1 / A2: Supply voltage for control terminals
Input IN to switch the motor on and off
Output 13, 14: For signaling the operating state ON or RUN (parameterizable (Page 99))
Output 23, 24: To signal operating state BYPASSED
Output 95, 96, and 98 to signal warnings and faults
Dependent on the variant of the 3RW50 soft starter:
Thermistor motor protection T11 / 21, T12, and T22: Connection of a temperature sensor
•
(optional)
T11 / T21 - T22: Connection for Thermoclick
T11 / T21 - T12: Connection for PTC Type A
Analog output AQ-, AQ I+ and AQ U+: Connection of an evaluation unit to display the motor
•
current (optional, average phase current in %)
AQ- / AQ U+: For evaluation units with output signal type Voltage:
Signal range 0 - 10 V
AQ- / AQ I+: For evaluation units with output signal type Current:
Signal range 4 - 20 mA (factory setting)
Main circuit connection load (motor) 2 / T1, 4 / T2, 6 / T3
SIRIUS 3RW50 soft starter
Manual, 09/2019, A5E35628455002A/RS-AA/001