Siemens SIRIUS 3RW50 Manual page 70

Industrial controls, soft starters and semiconductor switching devices
Table of Contents

Advertisement

Connecting
4.1 Connections
Note
Parameterizing output 13 / 14
You will find more information on parameterization in Chapter Parameterizing output 13 / 14
(output signal ON or RUN) (Page 99).
Note
Parameterizing the analog output
You can parameterize the output of the analog output with the 3RW5 HMI High Feature
(Page 111).
70
Main circuit connection network 1 / L1, 3 / L2, 5 / L3
A1 / A2: Supply voltage for control terminals
Input IN to switch the motor on and off
Output 13, 14: For signaling the operating state ON or RUN (parameterizable (Page 99))
Output 23, 24: To signal operating state BYPASSED
Output 95, 96, and 98 to signal warnings and faults
Dependent on the variant of the 3RW50 soft starter:
Thermistor motor protection T11 / 21, T12, and T22: Connection of a temperature sensor
(optional)
T11 / T21 - T22: Connection for Thermoclick
T11 / T21 - T12: Connection for PTC Type A
Analog output AQ-, AQ I+ and AQ U+: Connection of an evaluation unit to display the motor
current (optional, average phase current in %)
AQ- / AQ U+: For evaluation units with output signal type Voltage:
Signal range 0 - 10 V
AQ- / AQ I+: For evaluation units with output signal type Current:
Signal range 4 - 20 mA (factory setting)
Main circuit connection load (motor) 2 / T1, 4 / T2, 6 / T3
SIRIUS 3RW50 soft starter
Manual, 09/2019, A5E35628455002A/RS-AA/001

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents