Siemens SIRIUS 3RW50 Manual page 150

Industrial controls, soft starters and semiconductor switching devices
Table of Contents

Advertisement

Functions
7.12 3RW5 HMI High Feature
Process image input (PII)
Process data
DI 0.0
DI 0.1
DI 0.2
DI 0.3
DI 0.4
DI 1.0
DI 1.1
DI 1.2
DI 1.3
DI 1.4
DI 1.5
DI 1.6
DI 1.7
DI 2.0
DI 2.4
DI 2.5
DI 2.6
DI 2.7
DI 3.0
DI 3.1
DI 3.2
DI 3.3
DI 3.4
AI 4 (Float32)
AI 8 (Float32)
AI 12 (Float32)
Process image output (PIQ)
Process data
DQ 0.0
DQ 0.3
DQ 0.5
DQ 3.0
Further information
You will find further information on transferring the process images via a fieldbus in the
device manual for the respective 3RW5 communication module.
150
Process image
Ready (automatic)
Motor On
Group error
Group warning
Input 1
Motor current Iact-bit0
Motor current Iact-bit1
Motor current Iact-bit2
Motor current Iact-bit3
Motor current Iact-bit4
Motor current Iact-bit5
Manual operation local
Ramp operation
Motor CW
Starting mode active
Operation / bypass active
Stop mode active
Test operation active
Thermal motor model overload
Temperature sensor overload
Switching element overload
Cooling time active
Device error
Measured value 1 (factory setting: Phase current I L1 (rms))
Measured value 2 (factory setting: Phase current I L2 (rms))
Measured value 3 (factory setting: Phase current I L3 (rms))
Process image
Motor CW
Reset
Self-test (user-test)
Manual operation local - input controlled
SIRIUS 3RW50 soft starter
Manual, 09/2019, A5E35628455002A/RS-AA/001

Hide quick links: