PROFIenergy inhibit and pause time

Block PROFIenergy
If you set p5611.0 = 1, you inhibit the response of the inverter to PROFIenergy control
commands. In this case, the converter ignores the PROFIenergy control commands.
Pause time
● Minimum pause time: p5602
– When the pause time, which is sent using command "Start_Pause", is equal to or
– If the pause time is less than p5602[1], the inverter ignores the command.
● Maximum duration: p5606
11.3.10.6

Function diagrams and parameters

Function diagrams (see SINAMICS S120/S150 List Manual)
• 2381
• 2382
• 2610
Overview of important parameters (see SINAMICS S120/S150 List Manual)
• r5600
• p5602[0...1]
• p5606[0...1]
• p5611
• r5613.0...1
852
greater than the value in p5602[1], then the inverter goes into the energy-saving
mode.
PROFIenergy - Control commands / query commands
PROFIenergy - States
Sequence control - Sequencer
Pe hibernation ID
Pe hibernation pause time, minimum
Pe hibernation duration, maximum
Pe energy-saving properties, general
CO/BO: Pe energy-saving active/inactive
Function Manual, 11/2017, 6SL3097-4AB00-0BP5