Profinet-Based Diagnostics - Siemens SINAMICS S120 Function Manual

Drive functions
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

11.1.5.1

PROFINET-based diagnostics

For PROFINET, to transfer PROFIdrive message classes, channel diagnostics (Channel
Diagnosis) are used (see PROFINET IO specification (http://www.profibus.com)).
A message always comprises the following components in this specific sequence:
● Block Header (6 Byte)
– Blocktype
– Blocklength
– BlockversionHigh
– BlockversionLow
● API (4 Byte)
● Slot Number (2 Byte)
● Sub Slot Number (2 Byte)
● Channel Number (2 Byte)
● Channel Properties (0x8000) (2 Byte)
● User Structure Identifier (2 Byte)
● Channel Diagnosis Data (6 Byte)
– Channel Number (2 Byte)
– Channel Properties (2 Byte)
– Channel Error Type (2 Byte)
Overview:
Figure 11-10 Components of a message
Drive functions
Function Manual, 11/2017, 6SL3097-4AB00-0BP5
11.1 Communication according to PROFIdrive
Communication
767