Basic information about the drive system
13.4 BICO technology: Interconnecting signals
Note
A connector input (CI) cannot be interconnected with any connector output (CO, signal
source). The same applies to the binector input (BI) and binector output (BO).
For each CI and BI parameter, the parameter list shows under "data type" the information on
the data type of the parameter and the data type of the BICO parameter.
For CO parameters and BO parameters, only the data type of the BICO parameter is shown.
Notation:
• Data type BICO input: Data type parameter/Data type BICO parameter
Example: Unsigned32 / Integer16
• Data type BICO output: Data type BICO parameter
Example: FloatingPoint32
The possible interconnections between the BICO input (signal sink) and BICO output (signal
source) are listed in the table titled "Possible combinations for BICO interconnections"
, which can be found in the "Explanations on the parameter list" section of the SINAMICS
S120/S150 List Manual.
The BICO parameter interconnection can be implemented in different command data sets
(CDS). The different interconnections are activated by switching data sets. Interconnections
across drive objects are also possible.
13.4.3

Internal coding of the binector/connector output parameters

Internal coding is required for writing BICO input parameters via PROFIBUS, for example.