Inverter Protections; Smart Inverter Functions (Default State) - YASKAWA Solectria PVI 25TL-208 Installation And Operation Manual

Commercial 1000vdc string inverters
Table of Contents

Advertisement

Installation and Operation Guide SOLECTRIA® PVI 25TL-208, PVI 50TL-480 and PVI 60TL-480

Inverter Protections

OUTPUT MONITORING
ANTI-ISLANDING
OVER VOLTAGE PROTECTION
OVER CURRENT PROTECTION
GROUND MONITORING
SHORT CIRCUIT PROTECTION
ARC FAULT
LEAKAGE CURRENT MONITORING
TEMPERATURE MONITORING
KVA OVERHEAD
LOAD REJECTION OVER VOLTAGE (LROV)
PROTECTION
NO NEUTRAL REQUIRED
RAPID SHUTDOWN
CONTINUOUSLY MONITORED VARIABLES

Smart Inverter Functions (default state)

PARAMETER
ANTI-ISLANDING
LOW/HIGH VOLTAGE RIDE-THROUGH
LOW/HIGH FREQUENCY RIDE-THROUGH
DYNAMIC VOLT/VAR
RAMP RATES
FIXED POWER FACTOR
SOFT START RECONNECTION
FREQUENCY-WATT
VOLT-WATT
ACTIVE POWER CURTAILMENT
DOCR-071030-A (10/7/2022)
AC output voltage and frequency monitoring
Bidirectional frequency perturbation based on Sandia
Frequency Shift Detection
Integrated input and output over-voltage protection
Input and output over-current protection
DC input insulation to ground monitoring
AC and DC short circuit protection
DC series arc fault detection and circuit interruption
Leakage current to ground monitoring
Internal enclosure temperature monitoring
IGBT power module temperature monitoring
kVA overhead to produce rated Active Power at 0.91
power factor
Protection from LROV events
No neutral connection required
PVRSS certified rapid shutdown compliant to 2017 NEC
DC input insulation resistance with respect to ground
Third harmonic injection
AC output voltage and frequency
Leakage current to ground
Internal enclosure temperature
IGBT power module temperature
STANDARD
Enabled
Not Activated
Not Activated
Not Activated
Not Activated
Not Activated
Not Activated
Not Activated
Not Activated
Not Activated
RULE 21
Enabled
Enabled
Enabled
Enabled
Enabled
Not Activated
Enabled
Enabled
Enabled
Not Activated