Checking the Core ID switches
Table 3
Core module ID switch settings (System Utility card)
Core 0
Core 1
Preparing and planning for the upgrade
Procedure 2
Checking the Core ID switches
Each NT4N40 Core/Net card cage or module (see Figure 5 on
identified as "Core 0" or "Core 1". This setting is made by a set of option
switches on the System Utility card (see Figure 6 on
switches are set in the factory. Confirm that these settings match the
identification labels for the module into which they will be installed.
CAUTION — Service Interruption
The CP Core/Net card cages MUST be installed in the
correct Core 0 or Core 1 module.
1
Pull the System Utility card (NT4N48) far enough out of its slot so you can
see the ID switch settings.
2
Check and confirm the switch settings according to Table 3, "Core module
ID switch settings (System Utility card)," on page 33.
3
Reinstall the System Utility card.
a.
Gently slide the card into the slot until it makes contact with the
backplane. Never force a card into the slot.
b.
Push in the top and bottom latches on the card to lock it in place.
Position 1
On
Off
.
End of Procedure
Position 2
On
On