Current reference selection
After changing DIP switch (V/I switch of SW2) to the "I" side, PRESS
digital operator, then set the following parameters.
Current reference (4-20mA) parameter n004=3
Current reference (0-20mA) parameter n004=4
Frequency reference gain (n060)/bias (n061) can be set even when current reference
input is selected. For details, refer to "Adjusting frequency setting signal" on page 81.
84
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
on the
PRGM
Press the digital operator keys to run or stop
the inverter. Switch run and stop direction by
setting F/R LED.
Set frequency by the analog current signal
[0-100% (max frequency)/4-20mA]
connected to the control circuit terminal.
Set run/stop and FWD/REV run with
switching device connected to the control
circuit terminal.
Multi-function input terminals S1 and S2 are
set to Forward run / STOP (n050 = 1) and
Reverse run/stop (n051 = 2) respectively.
Set frequency by the analog current signal
[0-100% (max. frequency)/4-20mA]
connected to the control circuit terminal.