Alarm Display
Digital
RUN (Green)
Operator
ALARM (Red)
136
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Inverter
Explanation
Status
Corrective Actions
EF‰
Check the external
(External fault)
circuit (sequence).
Inverter receives an external
fault input from control circuit
terminal.
EF0: External fault reference
through MEMOBUS
communications
EF1: External fault input
command from control
circuit terminal S1
EF2: External fault input
command from control
circuit terminal S2
EF3: External fault input
command from control
circuit terminal S3
EF4: External fault input
command from control
circuit terminal S4
EF5: External fault input
command from control
circuit terminal S5
Protective
EF6: External fault input
Operation
command from control
circuit terminal S6
Output is shut
EF7: External fault input
OFF and motor
command from control
coasts to a
circuit terminal S7
stop.
CPF-00
Cycle power after
Inverter cannot communicate
checking the digital
with the digital operator for 5
operator is securely
sec. or more when power is
mounted.
turned ON.
If the fault remains,
replace the digital
operator or inverter.
CPF-01
Cycle power after
Transmission fault occurred
checking the digital
for 5 sec. or more when
operator is securely
transmission starts with the
mounted.
digital operator.
If the fault remains,
replace the digital
operator or inverter.
CPF-04
• Record all parameter
EEPROM fault of inverter
data and initialize the
control circuit is detected.
parameters. (Refer
to page 32 for
parameter
initialization)
• Cycle power.
If the fault remains,
replace the inverter.
Causes and