Using analog output (AM-AC) as a pulse train signal output (n065)
Analog output AM-AC can be used as a pulse train output (output frequency monitor).
Set n065 to 1 when using pulse train output.
Parameters No.
n065
Monitor output type selection
n065 setting
n065 Setting
0
Analog monitor output
Pulse monitor output
1
(Output frequency monitor)
Pulse train signal can be selected by setting n150.
n150 Setting
0
1440Hz / Max. frequency (n011)
1
1F: Output frequency x 1
6
6F: Output frequency x 6
12
12F: Output frequency x 12
24
24F: Output frequency x 24
36
36F: Output frequency x36
At the factory setting the pulse of 1440Hz can be output when output frequency is
100%
Pulse monitor output can be adjusted with the parameter n067.
66
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Name
Unit
Setting range
1
0,1
Description
Initial Setting
0