YASKAWA VS-606V7 Series Instruction Manual page 70

Compact general-purpose inverter
Hide thumbs Also See for VS-606V7 Series:
Table of Contents

Advertisement

Reducing Motor Noise or Leakage Current (n080)
Frequency setting varies according to inverter capacity (kVA).
Voltage Class (V)
200
Single-phase 3-
phase
400
3-phase
(1) Reduce continuous output current when changing carrier frequency to
(2) If the wiring distance is long, reduce the inverter carrier frequency as
Wiring Distance between
Inverter and Motor
Carrier frequency
(n080 setting)
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Initial Setting
Maximum
Capacity
Continuous
Carrier
(kW)
Output Current
Setting
Frequency
(A)
0.1
4
10kHz
0.8
0.2
4
10kHz
1.6
0.4
4
10kHz
3.0
0.7
4
10kHz
5.0
1.5
3
7.5kHz
8.0
2.2
3
7.5kHz
11.0
3.7
3
7.5kHz
17.5
5.5
3
7.5kHz
25
7.5
3
7.5kHz
33
0.2
3
7.5kHz
1.2
0.4
3
7.5kHz
1.8
0.7
3
7.5kHz
3.4
1.5
3
7.5kHz
4.8
2.2
3
7.5kHz
5.5
3.0
3
7.5kHz
7.2
3.7
3
7.5kHz
8.6
5.5
3
7.5kHz
14.8
7.5
3
7.5kHz
18
4 (10kHz) for the 200V class (1.5 W or more) and 400V class invert-
ers. Refer to the table above for the reduced current.
[Operation Condition]
•Input power supply voltage : 3-phase 200 to 230 V (200V class)
Single-Phase 200 to 240V (200V class)
3-Phase 380 to 460V (400V class)
•Ambient temperature:
14 to 122ºF (-10 to +50ºC)
(Protection structure: open chassis type
IP20)
described below
Up to 50m
Up to 100m
More than 100m
10kHz or less
5kHz or less
2.5kHz or less
(n080=1, 2, 3, 4, 7, 8, 9)
(n080=1, 2, 7, 8, 9)
(n080=1, 7, 8, 9,)
Reduced
Current (A)
7.0
10.0
16.5
23
30
1.0
1.6
3.0
4.0
4.8
6.3
8.1
*
17
69

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents