Voltage Class
Model
CIMR-V7*C‰‰‰‰
Status Indicator LED
Digital Operator
Terminals
Wiring Distance between
Inverter and Motor
Enclosure
Cooling Method
Ambient Temperature
Humidity
Storage Temperature*
Location
Elevation
Vibration
* Temperature during shipping (for short period)
# For details, refer to "Reducing motor noise or leakage current (n080)" on
page 68.
144
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
400V 3-phase
3-phase
40P2 40P4 40P7 41P5 42P2 43P0 43P7 45P5 47P5
Single-phase
RUN and ALARM provided as standard LEDs
Available to monitor frequency reference, output
(JVOP-140)
frequency, output current
Main circuit: screw terminals
Control circuit: plug-in screw terminal
328ft (100m) or less#
Open chassis IP20, Open chassis IP20 (Top-closed type),
or enclosed wall-mounted NEMA 1
Cooling fan is provided for the following models: 400V,
1.5kW or larger inverters (3-Phase)
Others models are self-cooling
: -10 to +50 °C (14 to 122°F)
Open chassis IP20
Open chassis IP20 (Top-closed type) and enclosed
wall mounted NEMA1.
: -10 to +40°C (14 to 105°F)
(not frozen)
95% RH or less (non-condensing)
-4 to 140°F (-20 to +60°C)
Indoor (free from corrosive gases or dust)
3280ft (1000m) or less
2
Up to 9.8m / S
(1G) at less than 20Hz, up to 2m / S
(0.2G) at less than 20 to 50Hz
2