YASKAWA VS-606V7 Series Instruction Manual page 169

Compact general-purpose inverter
Hide thumbs Also See for VS-606V7 Series:
Table of Contents

Advertisement

CE Conformance - Electro-Magnetic Compatibility (EMC)
In order to conform to EMC standards, exclusive-use methods are required for line
filter application, cable shielding and inverter installation. An outline of the methods
follows.
The line filter and the inverter must be mounted on the same metal plate. The filter
should be mounted as close to the inverter as practical. Keep cable as short as possible.
The metal plate should be securely grounded. The ground of the line filter and inverter
must be bonded to the metal plate with as much area as possible.
For line power input cable, screened cable is recommended at least within the panel.
The screen of the cable should be connected to a solid ground. For the motor cable,
screened cable (max. 20m) must be used and the screen of the motor cable is connected
to ground at both ends by a short connection, using as large an area as practical.
For a more detailed explanation, please refer to Making YASKAWA Inverter Products
Confirm with EMC Directive (G-TI#99012-V7).
The following table and figures show the line filter list for EMC standards and the
installation/wiring of inverter and line filter.
Line Filter List for EMC Conformance
Recommended Line Filters for VS-606 made by Rasmi Electronics Ltd
( 200V single phase )
VS-606V7
CIMR-V7AUB0P1
CIMR-V7AUB0P2
CIMR-V7AUB0P4
CIMR-V7AUB0P7
CIMR-V7AUB1P5
CIMR-V7AUB2P2
CIMR-V7AUB3P7
Rated Voltage: AC 250V single phase
Ambient Temperature: 40°C (max.)
168
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Compliance
Current
Weight
Model
(A)
(kg)
RS 1010-V7
10
0.6
RS 1020-V7
20
1.0
RS 1030-V7
30
1.1
RS 1040-V7
40
1.2
Dimension
W×D×H
71 x 45 x 169
111 x 50 x 169
144 x 50 x 174
174 x 50 x 174

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents