Appendix
12.3.5
System configuration 51
BMS – burner output
Fig. 12.10 System configuration 51 - BMS - burner output
Input E2
q
BMS %
w
– Burner starts subject to demand from the external controller (cycle block and soft start inactive).
– Feed/heating circuit pump enabled as a feed pump from 2 V.
– No temperature control
– Input E2:
Control 0 - 10 V by external controller
0 - 2 V burner OFF,
2-10 V burner output min. to max. within the programmed limits
12.3.6
System configuration 52
BMS – set boiler temperature
Fig. 12.11 System configuration 52 - BMS - set boiler temperature
Input E2
q
BMS %
w
– Burner starts subject to demand from the boiler thermostat (cycle block and soft start active).
– Feed/heating circuit pump enabled as a feed pump from 2 V.
– Boiler temperature controller
– Input E2:
Control by external controller with 0 - 10 V
0 - 2 V burner OFF
2-10 V set boiler temperature BTmin (HG21) - BTmax (HG22)